hi I have a problem with it reading only 0.01000v on the phases this applies to 3 phase 240V. I do not have a neutral leader. I use these transformers....

Howdy, I recently picked up some of the SCT-024 200A CTs from your shop. I spent this evening debugging some weird measurement behavior where low currents (below 20-30A) were accurate,...

Documention

NOTE: This was for an issue in previous revisions, but sill would be good practice. Consider adding an appropriately small fuse to prevent "runaway" situations with the power adapter. The...

enhancement

I decided to go the way of MQTT and InfluxDB and shut down my emon server. The webUI did not allow me to unset the emoncms values and shutting down...

bug

My MQTT broker requires that I specify specific `clientId` in order to connect. It would be nice if this was supported. After a quick look, I saw that AsyncMqttClient supports...

enhancement

Hi, I need use CT sensor SCT-013 20A/1V .. can i use this CT ? if I can I need know CurrentGain constant for this sensor. I will measure AC...

Hi! I brought the kit from Mouser which has the SCT016-A16 CT clamps. I have plugged into the board and had to add my own 9V transformer as the kit...

But what about 240V and 60Hz? _Originally posted by @netomx in https://github.com/CircuitSetup/Split-Single-Phase-Energy-Meter/issues/7#issuecomment-537653582_

bug

Hi CircuitSetup, I'm really enjoying my Split Single Phase Energy meter, with only one issue - every now and then, approximately every 10 days, it disappears from the network, and...

bug

The list of available WiFi networks does not populate when there is a SSID visible that contains 1 or more Unicode Characters.