Split-Single-Phase-Energy-Meter icon indicating copy to clipboard operation
Split-Single-Phase-Energy-Meter copied to clipboard

240V and 60Hz?

Open CircuitSetup opened this issue 4 years ago • 4 comments

But what about 240V and 60Hz?

Originally posted by @netomx in https://github.com/CircuitSetup/Split-Single-Phase-Energy-Meter/issues/7#issuecomment-537653582

CircuitSetup avatar Dec 03 '19 14:12 CircuitSetup

I can confirm this board and software works for split phase 240V at 60hz in North America (most people think there are 2 phases when it is split phase, but true 2 phase is quite rare as if you have more than 1 phase, you generally have 3 phases 120° offset). Just make sure you set the calibration values as recommended for 60hz and the chosen transformer.

chaseadam avatar Oct 02 '20 01:10 chaseadam

I can confirm this board and software works for split phase 240V at 60hz in North America (most people think there are 2 phases when it is split phase, but true 2 phase is quite rare as if you have more than 1 phase, you generally have 3 phases 120° offset). Just make sure you set the calibration values as recommended for 60hz and the chosen transformer.

What transformer did you use? I havent found anything with 240V

netomx avatar Dec 28 '20 22:12 netomx

I stuck with measuring just one of the two legs for the voltage (so a 120v transformer).

Ideally each leg is measured individually. Measuring between the legs (240v) is no better than measuring one leg as current flows through the neutral in a split system.

I do not have the reference, but I recall reading that there is negligible gain by measuring individual legs. I can imagine if you have a severely unbalanced panel it may make a difference.

chaseadam avatar Dec 28 '20 23:12 chaseadam

I've seen 125V on one phase and 108V on the other phase (at the same time) on my panel in real scenarios. Also, when combined, I've commonly seen 205-218V, so likely 120* offset (the building is 3-phase, each unit gets 2 of the three phases). In any case, I think metering one phase and multiplying by a constant would be very inaccurate in my situation.

missmah avatar Dec 04 '21 08:12 missmah