@kennyschuoler How did you manage to read the values of the Smart EVSE ? I have also fw 2.30 installed but can't get any values via modbus from the smartevse,...
Yes I did, no 1 is the evse, 11 is the sdm630 for the EV and 12 is for the mains including PV. ________________________________ Van: Michael Stegen ***@***.***> Verzonden: Monday,...
Yes it is fine, it worked fine for a couple of months but now it is a disaster. Also reading the MODBUS registers with an external Iobroker gateway works fine.
In the mean time I found that when I disconnect the iobroker gateway (which polls data every 10seconds), the Smart EVSE works as it should. To me it looks like...
Thanks, yes I will try next time with 60 seconds updates ________________________________ Van: Robert Heel ***@***.***> Verzonden: Monday, February 28, 2022 5:33:07 PM Aan: SmartEVSE/smartevse ***@***.***> CC: rvdgaag ***@***.***>; Author...
Ok topic can be closed, the to frequent data requests caused collisions so the smart else did not receive the data from the SDM-630 and cut off the power. Thanks...
Have a look here: https://github.com/serkri/SmartEVSE-3/releases/tag/v1.1.0-serkri-v3
Noticed here the same, I'll see what happens. I have an error message now since the upgrade to 3.8 (H43 zone 1 sensor error). Don't know if it is related...
The Heishamon large and CZ-TAW1 are working in parallel in my setup, both connected to an individual wired ethernet cable. After downgrading to the latest production version, 3.6, the sensor...
**update**, could not wait, the Heishamon works fine powered with the CZ-TAW1 together. The issue with the SG contacts on the CZ-NS5P were caused by me by faulty wiring from...