I am running 1.3.9a I will perform serial logging with that version

Thank you for this, I have run the serial logger as you requested and attached the file. I started the pump and several aux devices and then shut them down....

since I have installed 1.3.9a I thought I would repeat the exercise of starting the keypad after starting AqualinkD. I have turned on the debugging log and pasted both the...

I set the id to 0x08 and disconnected the keypad. No change from previous scenarios unresponsive. I plugged in the keypad while AqualinkD was running and cycled some equipment from...

After thinking about it I worried that connecting the keypad may not be obvious in the log and you might prefer a log that just showed what happened with no...

I will plug the PI directly into the same wires as keypad and report back

I connected the wires directly to the cable from the PureLink system. The one thing that is different from Aqualink is that PureLink comes with a 485 multiplex card that...

your confirmation that AqualinkD was doing the same initialization sequence as the keypad gave me an ID to test. What if AqualinkD was receiving all of the bus traffic but...

upon closer inspection the multiplex board I have is actually just a multiple bus connection card. I have attached pictures of front and back. I also have attached pictures of...

Additional test results ran test with everything but AquaPure board on 485 bus and cycled equipment with AqualinkD i added Aquapure without shutting down and it stopped responding. I have...