Here it is: EMS-ESP version 2.2.0 Boiler: BK13/BK15/Smartline/GB1x2 (DeviceID:0x08, ProductID:64, Version:03.06) Heating active: on Warm water/DHW active: off Service code: -H Service code number: 200 Selected flow temperature: 57 °C...

Waiting on telnet, I also got some crc errors. Random interval, 15s/1min Dashboard/Ems status is reporting 100% on RX but 99% on TX line quality e003+02:52:01.142 E 14: [telegram] Rx:...

I did try to set circulation "always on" from RC35 but no effect Anyway I'm going to try

I did try to set TX mode to 0 and restart everything, but nothing changed I'm not aware of how to reset boiler to factory settings. I have a concern...

The only thing I did touch is "Boiler Comfort Mode" as exposed on Domoticz through MQTT It is showing "Hot" as value. I did try to change it, and after...

How can I check if "call boiler wwcircmode 7" is effective ? I got no error on the command but if I show values I still see 2x3 min on...

Supposing RC35 is overwriting, I found RC35 service manual and I set recirculation mode to continuous Now it is reported correctly. "Warm water circulation pump freq: continuous" I'll post if...

I confirm is on now. Lets see if warm water is better. ![image](https://user-images.githubusercontent.com/58774150/109416260-69753180-79bd-11eb-8728-bc7a54d8a4af.png)

> Are you still on tx-mode 0? Then setting commands do not work. > RC35 service menu is used to change all settings including boiler. The "circ pump frequ" in...

Changed by service menu Now max allowable is 80°C and set is 70°C. Also reported 70 on show command The "feeling" at full hot is like before, but still kind...