I have been told my Inverter export limit was set to 3600 (and confirmed by GivEnergy in line with SSEN requirements) and I thought I should set the export limit...
Unfortunately my DNO (SSEN) has not authorised 6000, but only 3600. I have checked with GivEnergy Support and they have set export to 3600 and discharge to 3198, but predbat...
Yes it is an AIO. I have now double checked with GivEnergy Support and they say I definitely have the export limit set to 3600. They have also set a...
Thx. I have set_read_only to On (and left mode to charge & discharge). I have manually set a charge for two hours time (2.5 hours) and set a discharge for...
With read only on. And setting charge/export on the AIO manually. It still peaked at 6000. So I turned Predbat/HA machine off completely and re-ran the test with the same...
Yes, not Predbat. Told to update firmware which succeeded 2nd time, just ran another export still @6000. Will get back to support this pm. Agreed! Had "fun" with DNO (SSEN)...
Think I have confirmation of the solution from GivEnergy Support. The setting "Enable Export Limit (G100)" - has been set to "true" My export is now limited to 3600! I...