[bug] - min_cycle_duration ignored
When setting min_cycle_duration to either seconds: 120 or minutes: 2 I get the same results with my cooling turning off/on every few seconds if the temperature is close to the setpoint.
Is there something I'm missing? I copied it straight from the example config and it still doesn't work as intended.
I second this same issue. I have noticed that the A/C will cut on and off every few seconds when close to set point. The biggest issue with this is that the A/C compressor can go out a lot quicker when being cut on and off so quickly and so much. What is the best fix for this?
This could be fixed by PR #37
Please let us know if v0.7.0 fixed it. Thanks @ollo69 !
Thanks a lot, @ollo69 but I have checked the min_cycle_duration is not working since v0.6.7. EDIT: It is working in v0.7.1
Asap the temp reaches the target, it stops without checking the min_cycle_duration configuration.
I have tested a bit more, it stops when low/high temperature changes, and then it calls _async_control_climate(force=True) which makes sense to force the stopping or starting of the device when the targets change.
Ok, I have to adapt my automations, but it is working. Thanks a lot again @ollo69
"min_cycle_duration" is not working in the last release (0.9.1). It is constantly stopping my AC machines. I only see one "weird" log that says my cooler is "Already running". I see in logs that "keep_alive" is working but... I have no "keep_alive" configuration in my YAML. In logs (debug level) I see the following every few seconds:
`2023-08-23 14:46:52.668 DEBUG (MainThread) [custom_components.dual_smart_thermostat.climate] _async_control_climate_forced, time 2023-08-23 12:46:52.667375+00:00
2023-08-23 14:46:52.668 DEBUG (MainThread) [custom_components.dual_smart_thermostat.climate] _async_control_heat_cool
2023-08-23 14:46:52.669 INFO (MainThread) [custom_components.dual_smart_thermostat.climate] Keep-alive - Toggling on heater cooler switch.oficina_heater, switch.oficina_cooler`
Could it be related in some way to the new opening configuration and the new timing feature?
Thanks in advance for your help.
it doesn't work for me, using v0.9.5 installed from hacs, using latest HA 2024.5.2 I have a setup to try out dual smart thermostat:
climate:
- platform: dual_smart_thermostat
name: Bedroom AC
heater: input_boolean.bedroom_ac_heat_toggle
cooler: input_boolean.bedroom_ac_cool_toggle
heat_cool_mode: true
target_sensor: input_number.fake_temp
min_temp: 17
max_temp: 28
cold_tolerance: 1.5
hot_tolerance: 1.5
min_cycle_duration:
minutes: 2
keep_alive:
minutes: 3
precision: 0.1
target_temp_step: 0.5
and it switches off heating no matter how much time passed.
here is a preview of history, less then a minute passed from heat start and it switched off, even though 2 minutes are set as minimum cycle duration.
I have tried to look it up in states, what value climate entity has, but there isn't one. Is that by design or does that mean that my configuration is wrong?