Yes, the settings for each phase can be seen as attributes to the dynamic_circuit_limit sensor. So you would in your case be able to access it as: {{ state_attr('sensor.easee_vorgarten_dynamic_circuit_limit', 'state_dynamicCircuitCurrentP1'')...
I am a bit puzzled by what you are writing. Please try to describe in more detail what you have tried and why it is not working. I.e. what service...
There is some information on the easee developer page that is kind of required reading to understand what the different limits and functions actually does. (I guess we should link...
Hi and thank you. It is best to use dynamic circuit limit for this purpose. Changing the max circuit limit will write to flash in the device each time, so...
Dynamic circuit works the same way. The lowest value of all the limits "wins". So if your max circuit limit is set to 14A and the dynamic circuit limit is...
Please close the issue if this solved your problem.
As I said above, there are services within the Easee integration in HA which you can use to set the dynamic circuit limit. (And yes, the app supports only setting...
Ok, we should I guess provide some examples, but until then I can share how my setup looks. First I have some template sensors, one set for solar charging and...
The relation between power (W) and current (A) is power = voltage * current (P = U * I). If I make the assumption that you are on an electrical...
1. To be able to switch between 1 and 3-phase you need to have it set to automatic mode. The other modes forces 1 or 3-phase, which is not really...