Hi I have a PowerWalker VI 1500 RT HID, trying to use the usbhid-ups driver, but I do not see any commands:
Link: https://powerwalker.com/?page=product&item=10120023
$ upsc pw
Init SSL without certificate database
battery.charge: 100
battery.runtime: 5282
battery.type: PbAc
battery.voltage: 41
battery.voltage.nominal: 36
device.mfr: PPC
device.model: HID UPS
device.serial: 716317C00120
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: ffff
driver.parameter.vendorid: 06da
driver.version: 2.7.2
driver.version.data: Liebert HID 0.3
driver.version.internal: 0.38
ups.load: 18
ups.mfr: PPC
ups.model: HID UPS
ups.productid: ffff
ups.serial: 716317C00120
ups.status: OL CHRG
ups.vendorid: 06da
Output from /lib/nut/usbhid-ups -DD -a pw
0.000000 debug level is '2'
0.002392 upsdrv_initups...
0.003650 Checking device (174C/1153) (001/006)
0.003821 - VendorID: 174c
0.003868 - ProductID: 1153
0.003909 - Manufacturer: unknown
0.003949 - Product: unknown
0.003989 - Serial Number: unknown
0.004029 - Bus: 001
0.004067 Trying to match device
0.004117 Device does not match - skipping
0.004174 Checking device (06DA/FFFF) (001/005)
0.010156 - VendorID: 06da
0.010204 - ProductID: ffff
0.010245 - Manufacturer: PPC
0.010285 - Product: HID UPS
0.010324 - Serial Number: 716317C00120
0.010364 - Bus: 001
0.010403 Trying to match device
0.010563 Device matches
0.011565 HID descriptor length 1393
0.033784 Report Descriptor size = 1393
0.036523 Using subdriver: Liebert HID 0.3
0.037062 Path: UPS.BatterySystem.Battery.BatteryID, Type: Feature, ReportID: 0x20, Offset: 0, Size: 8, Value: 1
0.037555 Path: UPS.BatterySystem.Battery.ffff0090, Type: Feature, ReportID: 0x21, Offset: 0, Size: 8, Value: 3
0.038061 Path: UPS.BatterySystem.Battery.PresentStatus.Present, Type: Feature, ReportID: 0x27, Offset: 0, Size: 8, Value: 1
0.038141 Path: UPS.BatterySystem.Battery.PresentStatus.Present, Type: Input, ReportID: 0x27, Offset: 0, Size: 8, Value: 1
0.038217 Path: UPS.BatterySystem.Battery.PresentStatus.ffff0074, Type: Feature, ReportID: 0x27, Offset: 8, Size: 8, Value: 0
0.038292 Path: UPS.BatterySystem.Battery.PresentStatus.ffff0074, Type: Input, ReportID: 0x27, Offset: 8, Size: 8, Value: 0
0.038801 Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 1
0.040554 Path: UPS.BatterySystem.Battery.ffff00e3, Type: Feature, ReportID: 0xe3, Offset: 0, Size: 8, Value: 1
0.041067 Path: UPS.BatterySystem.Battery.ffff0045, Type: Feature, ReportID: 0x25, Offset: 0, Size: 32, Value: 2.4192e+06
0.041138 Path: UPS.BatterySystem.BatterySystemID, Type: Feature, ReportID: 0x20, Offset: 8, Size: 8, Value: 1
0.041206 Path: UPS.BatterySystem.Charger.ChargerID, Type: Feature, ReportID: 0x20, Offset: 16, Size: 8, Value: 1
0.041677 Path: UPS.BatterySystem.Charger.ffff0094, Type: Feature, ReportID: 0x26, Offset: 0, Size: 8, Value: 4
0.041757 Path: UPS.BatterySystem.Charger.PresentStatus.ffff0079, Type: Feature, ReportID: 0x27, Offset: 16, Size: 8, Value: 0
0.041832 Path: UPS.BatterySystem.Charger.PresentStatus.ffff0079, Type: Input, ReportID: 0x27, Offset: 16, Size: 8, Value: 0
0.041905 Path: UPS.BatterySystem.Charger.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x27, Offset: 24, Size: 8, Value: 0
0.041978 Path: UPS.BatterySystem.Charger.PresentStatus.InternalFailure, Type: Input, ReportID: 0x27, Offset: 24, Size: 8, Value: 0
0.042052 Path: UPS.BatterySystem.Charger.PresentStatus.Used, Type: Feature, ReportID: 0x27, Offset: 32, Size: 8, Value: 1
0.042125 Path: UPS.BatterySystem.Charger.PresentStatus.Used, Type: Input, ReportID: 0x27, Offset: 32, Size: 8, Value: 1
0.042555 Path: UPS.Flow.[1].ConfigFrequency, Type: Feature, ReportID: 0x14, Offset: 0, Size: 8, Value: 50
0.043060 Path: UPS.Flow.[1].ConfigVoltage, Type: Feature, ReportID: 0x15, Offset: 0, Size: 8, Value: 230
0.043561 Path: UPS.Flow.[1].FlowID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 1
0.044061 Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 1350
0.044141 Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x74, Offset: 16, Size: 16, Value: 1500
0.044679 Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 50
0.045179 Path: UPS.Flow.[4].ConfigPercentLoad, Type: Feature, ReportID: 0x16, Offset: 0, Size: 8, Value: 110
0.045680 Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x72, Offset: 0, Size: 8, Value: 230
0.045759 Path: UPS.Flow.[4].FlowID, Type: Feature, ReportID: 0x0b, Offset: 8, Size: 8, Value: 4
0.047442 Path: UPS.OutletSystem.Outlet.[1].FlowID, Type: Feature, ReportID: 0x80, Offset: 0, Size: 8, Value: 4
0.047525 Path: UPS.OutletSystem.Outlet.[1].OutletID, Type: Feature, ReportID: 0x80, Offset: 8, Size: 8, Value: 0
0.049313 Path: UPS.OutletSystem.Outlet.[1].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 0, Size: 8, Value: 0
0.051061 Path: UPS.OutletSystem.Outlet.[2].DelayBeforeShutdown, Type: Feature, ReportID: 0x8d, Offset: 0, Size: 32, Value: -1
0.052811 Path: UPS.OutletSystem.Outlet.[2].DelayBeforeStartup, Type: Feature, ReportID: 0x90, Offset: 0, Size: 32, Value: -1
0.052962 Path: UPS.OutletSystem.Outlet.[2].FlowID, Type: Feature, ReportID: 0x80, Offset: 16, Size: 8, Value: 4
0.053053 Path: UPS.OutletSystem.Outlet.[2].OutletID, Type: Feature, ReportID: 0x80, Offset: 24, Size: 8, Value: 1
0.053128 Path: UPS.OutletSystem.Outlet.[2].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 8, Size: 8, Value: 1
0.054812 Path: UPS.OutletSystem.Outlet.[2].PresentStatus.SwitchOn/Off, Type: Feature, ReportID: 0x82, Offset: 0, Size: 8, Value: 1
0.054890 Path: UPS.OutletSystem.Outlet.[2].PresentStatus.SwitchOn/Off, Type: Input, ReportID: 0x82, Offset: 0, Size: 8, Value: 1
0.056562 Path: UPS.OutletSystem.Outlet.[2].ffff005d, Type: Feature, ReportID: 0x87, Offset: 0, Size: 32, Value: -1
0.058313 Path: UPS.OutletSystem.Outlet.[2].ffff005e, Type: Feature, ReportID: 0x8a, Offset: 0, Size: 32, Value: 3
0.060062 Path: UPS.OutletSystem.Outlet.[3].DelayBeforeShutdown, Type: Feature, ReportID: 0x8e, Offset: 0, Size: 32, Value: -1
0.061811 Path: UPS.OutletSystem.Outlet.[3].DelayBeforeStartup, Type: Feature, ReportID: 0x91, Offset: 0, Size: 32, Value: -1
0.061894 Path: UPS.OutletSystem.Outlet.[3].FlowID, Type: Feature, ReportID: 0x80, Offset: 32, Size: 8, Value: 4
0.061974 Path: UPS.OutletSystem.Outlet.[3].OutletID, Type: Feature, ReportID: 0x80, Offset: 40, Size: 8, Value: 2
0.062049 Path: UPS.OutletSystem.Outlet.[3].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 16, Size: 8, Value: 1
0.062123 Path: UPS.OutletSystem.Outlet.[3].PresentStatus.SwitchOn/Off, Type: Feature, ReportID: 0x82, Offset: 8, Size: 8, Value: 1
0.062196 Path: UPS.OutletSystem.Outlet.[3].PresentStatus.SwitchOn/Off, Type: Input, ReportID: 0x82, Offset: 8, Size: 8, Value: 1
0.063941 Path: UPS.OutletSystem.Outlet.[3].ffff005d, Type: Feature, ReportID: 0x88, Offset: 0, Size: 32, Value: -1
0.065689 Path: UPS.OutletSystem.Outlet.[3].ffff005e, Type: Feature, ReportID: 0x8b, Offset: 0, Size: 32, Value: 6
0.067425 Path: UPS.OutletSystem.ffff00c0, Type: Feature, ReportID: 0xc0, Offset: 0, Size: 8, Value: 2
0.067501 Path: UPS.OutletSystem.OutletSystemID, Type: Feature, ReportID: 0x80, Offset: 48, Size: 8, Value: 1
0.069178 Path: UPS.PowerConverter.ffff0041, Type: Feature, ReportID: 0x4a, Offset: 0, Size: 8, Value: 1
0.069683 Path: UPS.PowerConverter.Input.[1].ffff0043, Type: Feature, ReportID: 0x73, Offset: 0, Size: 8, Value: 1
0.071432 Path: UPS.PowerConverter.Input.[1].ffff0094, Type: Feature, ReportID: 0xc1, Offset: 0, Size: 8, Value: 0
0.071934 Path: UPS.PowerConverter.Input.[1].FlowID, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 1
0.072436 Path: UPS.PowerConverter.Input.[1].Frequency, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 50
0.072515 Path: UPS.PowerConverter.Input.[1].InputID, Type: Feature, ReportID: 0x30, Offset: 8, Size: 8, Value: 1
0.074190 Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Feature, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
0.074274 Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Input, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
0.074348 Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Feature, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
0.074421 Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Input, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
0.074941 Path: UPS.PowerConverter.Input.[1].PresentStatus.FrequencyOutOfRange, Type: Feature, ReportID: 0x32, Offset: 0, Size: 8, Value: 0
0.075021 Path: UPS.PowerConverter.Input.[1].PresentStatus.FrequencyOutOfRange, Type: Input, ReportID: 0x32, Offset: 0, Size: 8, Value: 0
0.075127 Path: UPS.PowerConverter.Input.[1].PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x32, Offset: 8, Size: 8, Value: 0
0.075203 Path: UPS.PowerConverter.Input.[1].PresentStatus.VoltageOutOfRange, Type: Input, ReportID: 0x32, Offset: 8, Size: 8, Value: 0
0.075280 Path: UPS.PowerConverter.Input.[1].PresentStatus.ffff0078, Type: Feature, ReportID: 0x32, Offset: 16, Size: 8, Value: 0
0.075356 Path: UPS.PowerConverter.Input.[1].PresentStatus.ffff0078, Type: Input, ReportID: 0x32, Offset: 16, Size: 8, Value: 0
0.075432 Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 16, Size: 16, Value: 229
0.075936 Path: UPS.PowerConverter.Input.[3].ffff0046, Type: Feature, ReportID: 0x39, Offset: 0, Size: 8, Value: 0
0.076014 Path: UPS.PowerConverter.Input.[3].FlowID, Type: Feature, ReportID: 0x30, Offset: 16, Size: 8, Value: 3
0.076089 Path: UPS.PowerConverter.Input.[3].InputID, Type: Feature, ReportID: 0x30, Offset: 24, Size: 8, Value: 3
0.076572 Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Feature, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
0.076648 Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Input, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
0.077185 Path: UPS.PowerConverter.Input.[3].ffff0047, Type: Feature, ReportID: 0x3a, Offset: 0, Size: 8, Value: 1
0.077690 Path: UPS.PowerConverter.ffff0014.ffff0015, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 1
0.078188 Path: UPS.PowerConverter.ffff0014.PresentStatus.Used, Type: Feature, ReportID: 0x41, Offset: 0, Size: 8, Value: 0
0.078263 Path: UPS.PowerConverter.ffff0014.PresentStatus.Used, Type: Input, ReportID: 0x41, Offset: 0, Size: 8, Value: 0
0.079939 Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0074, Type: Feature, ReportID: 0x3e, Offset: 0, Size: 8, Value: 0
0.080016 Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0074, Type: Input, ReportID: 0x3e, Offset: 0, Size: 8, Value: 0
0.080089 Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0075, Type: Feature, ReportID: 0x3e, Offset: 8, Size: 8, Value: 0
0.080162 Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0075, Type: Input, ReportID: 0x3e, Offset: 8, Size: 8, Value: 0
0.080817 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x42, Offset: 0, Size: 16, Value: 192
0.080901 Path: UPS.PowerConverter.Output.ApparentPower, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 289
0.080971 Path: UPS.PowerConverter.Output.FlowID, Type: Feature, ReportID: 0x40, Offset: 8, Size: 8, Value: 4
0.081048 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x42, Offset: 32, Size: 16, Value: 50
0.081560 Path: UPS.PowerConverter.Output.ffff0053, Type: Feature, ReportID: 0x4d, Offset: 0, Size: 16, Value: 243
0.082059 Path: UPS.PowerConverter.Output.HighVoltageTransfer, Type: Feature, ReportID: 0x48, Offset: 0, Size: 16, Value: 276
0.082559 Path: UPS.PowerConverter.Output.ffff0050, Type: Feature, ReportID: 0x4e, Offset: 0, Size: 16, Value: 207
0.083064 Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 184
0.083145 Path: UPS.PowerConverter.Output.OutputID, Type: Feature, ReportID: 0x40, Offset: 16, Size: 8, Value: 1
0.083684 Path: UPS.PowerConverter.Output.PresentStatus.ffff004a, Type: Feature, ReportID: 0x49, Offset: 0, Size: 8, Value: 0
0.083759 Path: UPS.PowerConverter.Output.PresentStatus.ffff004a, Type: Input, ReportID: 0x49, Offset: 0, Size: 8, Value: 0
0.083837 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 48, Size: 16, Value: 228
0.083904 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x40, Offset: 24, Size: 8, Value: 1
0.084428 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
0.084933 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 8, Value: 1
0.085033 Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x0c, Offset: 8, Size: 8, Value: 2
0.085553 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 36
0.085629 Path: UPS.PowerSummary.ffff0095, Type: Feature, ReportID: 0x0b, Offset: 16, Size: 8, Value: 0
0.086056 Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: -1
0.086557 Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: -1
0.086633 Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x0c, Offset: 16, Size: 8, Value: 100
0.086704 Path: UPS.PowerSummary.FlowID, Type: Feature, ReportID: 0x0b, Offset: 24, Size: 8, Value: 4
0.086773 Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x0c, Offset: 24, Size: 8, Value: 100
0.087312 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
0.087389 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x10, Offset: 8, Size: 8, Value: 1
0.087464 Path: UPS.PowerSummary.ffff00f0, Type: Feature, ReportID: 0x10, Offset: 16, Size: 8, Value: 3
0.087536 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x10, Offset: 24, Size: 8, Value: 2
0.087609 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x10, Offset: 32, Size: 8, Value: 4
0.087682 Path: UPS.PowerSummary.ffff00f1, Type: Feature, ReportID: 0x10, Offset: 40, Size: 8, Value: 6
0.087756 Path: UPS.PowerSummary.ffff00f2, Type: Feature, ReportID: 0x10, Offset: 48, Size: 8, Value: 8
0.089433 Path: UPS.PowerSummary.ffff00e2, Type: Feature, ReportID: 0xe2, Offset: 0, Size: 8, Value: 12
0.089936 Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 19
0.090010 Path: UPS.PowerSummary.PowerSummaryID, Type: Feature, ReportID: 0x0b, Offset: 32, Size: 8, Value: 1
0.091680 Path: UPS.PowerSummary.ffff0094, Type: Feature, ReportID: 0xe1, Offset: 0, Size: 8, Value: 3
0.092187 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.092265 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.092338 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.092410 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.092482 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.092554 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.092625 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.092696 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.093187 Path: UPS.PowerSummary.PresentStatus.ffff0077, Type: Feature, ReportID: 0x03, Offset: 0, Size: 8, Value: 0
0.093265 Path: UPS.PowerSummary.PresentStatus.ffff0077, Type: Input, ReportID: 0x03, Offset: 0, Size: 8, Value: 0
0.093337 Path: UPS.PowerSummary.PresentStatus.Good, Type: Feature, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
0.093408 Path: UPS.PowerSummary.PresentStatus.Good, Type: Input, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
0.093933 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 0
0.094006 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x02, Offset: 0, Size: 8, Value: 0
0.094075 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Feature, ReportID: 0x02, Offset: 8, Size: 8, Value: 0
0.094143 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x02, Offset: 8, Size: 8, Value: 0
0.094237 Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
0.094306 Path: UPS.PowerSummary.PresentStatus.Overload, Type: Input, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
0.094373 Path: UPS.PowerSummary.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
0.094439 Path: UPS.PowerSummary.PresentStatus.OverTemperature, Type: Input, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
0.094936 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.095013 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.095087 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
0.095160 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
0.095234 Path: UPS.PowerSummary.Temperature, Type: Feature, ReportID: 0x07, Offset: 8, Size: 16, Value: 298.9
0.095306 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 24, Size: 16, Value: 41.1
0.097043 libusb_get_report: error sending control message: Operation not permitted
0.097114 Can't retrieve Report f0: Operation not permitted
0.097177 Path: UPS.ffff0010.[1].ffff00f0, Type: Feature, ReportID: 0xf0, Offset: 0, Size: 8
0.098916 libusb_get_report: error sending control message: Operation not permitted
0.098972 Can't retrieve Report f1: Operation not permitted
0.099032 Path: UPS.ffff0010.[1].ffff00f1, Type: Feature, ReportID: 0xf1, Offset: 0, Size: 8
0.099561 Path: UPS.ffff0010.[1].ffff00ff, Type: Feature, ReportID: 0xff, Offset: 0, Size: 8, Value: 0
0.099680 Report descriptor retrieved (Reportlen = 1393)
0.099724 Found HID device
0.099767 Detected a UPS: PPC/HID UPS
0.099898 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 24, Size: 16, Value: 41.1
0.099997 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 36
0.100112 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.100225 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
0.100339 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
0.101340 Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 19
0.101455 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.101551 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.101646 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.101739 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.101824 Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
0.101898 find_nut_info: unknown info type: load.off.delay
0.101942 find_nut_info: unknown info type: load.on.delay
0.101983 find_nut_info: unknown info type: load.off.delay
0.102055 upsdrv_initinfo...
0.102118 upsdrv_updateinfo...
0.184313 Got 2 HID objects...
0.184405 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
0.184503 Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 32, Value: 2927
0.184576 Quick update...
0.184642 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.184707 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.184772 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.184872 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
0.185113 dstate_init: sock /var/run/nut/usbhid-ups-pokoje open on fd 5
0.185200 upsdrv_updateinfo...
0.435446 libusb_get_interrupt: Connection timed out
0.435542 Got 0 HID objects...
0.435586 Quick update...
0.435656 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
0.435724 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
0.435790 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
0.435855 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
2.187000 upsdrv_updateinfo...
I also own this device. In the current git-version the MGE-HID driver claims this vendor/product id and actually delivers more values (eg support for the outlets) and command support:
upsc pw
Init SSL without certificate database
battery.charge: 100
battery.charger.status: floating
battery.energysave: no
battery.runtime: 6244
battery.type: PbAc
device.mfr: PPC
device.model: HID UPS Sinewave 1500VA UPS
device.serial: 716318C00018
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 15
driver.parameter.port: auto
driver.parameter.productid: ffff
driver.parameter.synchronous: no
driver.parameter.vendorid: 06da
driver.version: 2.7.4-708-g241848c3
driver.version.data: MGE HID 1.44
driver.version.internal: 0.43
input.frequency: 50.0
input.frequency.nominal: 50
input.transfer.boost.low: 207
input.transfer.high: 276
input.transfer.low: 184
input.transfer.trim.high: 243
input.voltage: 233.0
input.voltage.nominal: 230
outlet.1.delay.shutdown: 2147483647
outlet.1.delay.start: 3
outlet.1.desc: PowerShare Outlet 1
outlet.1.id: 1
outlet.1.status: on
outlet.1.switchable: yes
outlet.2.delay.shutdown: 2147483647
outlet.2.delay.start: 6
outlet.2.desc: PowerShare Outlet 2
outlet.2.id: 2
outlet.2.status: on
outlet.2.switchable: yes
outlet.desc: Main Outlet
outlet.id: 0
outlet.switchable: no
output.frequency: 50.0
output.frequency.nominal: 50
output.voltage: 233.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.firmware: 05649-0499
ups.load: 10
ups.load.high: 110
ups.mfr: PPC
ups.model: HID UPS Sinewave 1500VA UPS
ups.power: 152
ups.power.nominal: 1500
ups.productid: ffff
ups.realpower: 96
ups.realpower.nominal: 1350
ups.serial: 716318C00018
ups.start.auto: yes
ups.start.battery: yes
ups.status: OL CHRG
ups.temperature: 34.0
ups.test.interval: 2419200
ups.test.result: Done and passed
ups.timer.shutdown: -1
ups.timer.start: -1
ups.type: offline / line interactive
ups.vendorid: 06da
BUT: the online/onbatt status fluctuates:
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OL CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OB CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OB CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OL CHRG
During "quick poll" all is good, only a full-hid-scan sets it as offline.
The issue is, that the firmware of this device sends a "UPS.PowerConverter.Input.[3].PresentStatus.Used" during normal operations (AC present) and the original MGE sees this as on bat:
1201.398937 [D2] Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
1201.398985 [D5] hu_find_infoval: found online (value: 1)
1201.399027 [D5] process_boolean_info: online
1201.399065 [D4] Entering libusb_get_report
1201.399603 [D3] Report[get]: (2 bytes) => 3b 01
1201.399659 [D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.399704 [D5] Unit = 00000000, UnitExp = 0
1201.399740 [D5] Exponent = 0
1201.399784 [D2] Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Feature, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
1201.399830 [D5] hu_find_infoval: found !online (value: 1)
1201.399870 [D5] process_boolean_info: !online
1201.399925 [D3] Report[buf]: (6 bytes) => 01 01 00 01 00 01
1201.399968 [D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.400009 [D5] Unit = 00000000, UnitExp = 0
1201.400048 [D5] Exponent = 0
1201.400091 [D2] Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
1201.400135 [D5] process_boolean_info: !dischrg
1201.400190 [D3] Report[buf]: (6 bytes) => 01 01 00 01 00 01
1201.400233 [D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.400276 [D5] Unit = 00000000, UnitExp = 0
1201.400314 [D5] Exponent = 0
Can mge-hid.c be changed so that the "UPS.PowerConverter.Input.[3].PresentStatus.Used" is NOT applied/considered as offline for the specific manufacturer/model ups.mfr: PPC ups.model: HID UPS Sinewave 1500VA UPS ?
I could test, but lack coding skills to do that on my own.
I got the same problem as @mdillmann with PowerWalker VI 1000 ERT HID. onbatt and online status are fluctuating. Not possible to send notifications.
I tried to filter the events with upssched timer but no luck because when it is onbatt, sometimes it reports an online event between.
Is there a workaround or can we excpect a fix here?
Sep 07 14:05:58 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:06:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:06:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:06:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:06:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:07:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:07:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:07:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:07:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:08:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:08:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:08:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:08:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:09:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:09:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:09:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:09:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:10:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:10:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:10:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:10:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:11:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:11:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:11:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:11:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
@cuthulino : just in case, which version of NUT are you running? If it is a packaged one (e.g. old v2.7.4) then probably no fix is expected until distros update their recipes to deliver a newer NUT release. What you have packaged - is set in stone. If you're (open to) running a custom build, there's a chance :)
As I re-read this issue (and thanks to @mdillmann for analysis above), it sounded reminiscent of onlinedischarge feature added before NUT v2.8.0 (hence the question - maybe the new release does happen to address this behavior?), although upon closer reading into the code of that change at #811 and #1359 - maybe it does not and just is similar... similar enough to propose another toggle to either completely disable looking at that report as @mdillmann proposed, or to ignore !online from UPS.PowerConverter.Input.[3].PresentStatus.Used if UPS.PowerSummary.PresentStatus.ACPresent says we are online (and for good measure, if we are not discharging at the moment).
CC @aquette about whether/how this can be done in a sane manner? Move from mge_onbatt_info static mapping to a function like eaton_converter_online_fun from eaton_converter_online_info dynamic mapping, that would consider recent (timed to not expire) readings from those several data sources, and/or the user toggle to ignore some of the data sources?
Also generally, why would it flip? Is it a firmware bug to nag the vendor about, or does it reflect inner workings of that UPS way too honestly (e.g. some line-interactive "Power Converter" device really going "offline" so the UPS load is fed by the wall power directly, and this intimate knowledge is misinterpreted by NUT driver)?
@mdillmann @cuthulino : Also as for a local PoC fix, you can try to comment away (move under nearby #if 0) the mapping line https://github.com/networkupstools/nut/blob/master/drivers/mge-hid.c#L1251 and rebuild NUT locally. It should then ignore/not-query that information, so we can see if that ignorance generally helps with these devices.
Another idea is to swap the order of two neighboring lines, placing "ACPresent" after "Input[3]...Used" - so if both are served by the device, the "ACPresent" takes precedence (would be queried last), I suppose... Usually with named data points (not like "BOOL" here) is the opposite - the first successful reading wins, so we strive to list most relevant/precise/... mappings on top and fallbacks in the end.
And as a side note: curious how many mappings apply to "PowerWalker VI" series - here different versions of NUT covered it with Liebert and MGE mapping support, and in #1512 the device has a completely different vendor and product ID and so gets covered as a CyberPower (CPS) unit... There it is allegedly "PowerWalker VI 500 R1U" with a manufacturer field saying "1" :)
@jimklimov you are right. I am really running the old 2.7.4 from the packages.
I will try the 2.8.0 in the next days and report back, if the error persists.
@jimklimov I have the same Problem with 2.8.0
@warp735 : Same model? NUT 2.8.0 release or more recent (e.g. custom build from github master)?
@jimklimov sorry, just saw that it's still 2.7 (use Unraid) Yes, it's the same model and the same error.
@warp735 has since confirmed his VI 1000 RT HID working with NUT 2.8.0 on UNRAID see https://forums.unraid.net/topic/60217-plugin-nut-v2-network-ups-tools/?do=findComment&comment=1288104
I just upgraded to bookworm and can confirm it is working with the 1500 hid.