support for PowerWalker VI 1500 RT HID

Open goldie83 opened this issue 7 years ago • 6 comments

Hi I have a PowerWalker VI 1500 RT HID, trying to use the usbhid-ups driver, but I do not see any commands:

Link: https://powerwalker.com/?page=product&item=10120023

$ upsc pw
Init SSL without certificate database
battery.charge: 100
battery.runtime: 5282
battery.type: PbAc
battery.voltage: 41
battery.voltage.nominal: 36
device.mfr: PPC
device.model: HID UPS
device.serial: 716317C00120
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: ffff
driver.parameter.vendorid: 06da
driver.version: 2.7.2
driver.version.data: Liebert HID 0.3
driver.version.internal: 0.38
ups.load: 18
ups.mfr: PPC
ups.model: HID UPS
ups.productid: ffff
ups.serial: 716317C00120
ups.status: OL CHRG
ups.vendorid: 06da

Output from /lib/nut/usbhid-ups -DD -a pw

   0.000000     debug level is '2'
   0.002392     upsdrv_initups...
   0.003650     Checking device (174C/1153) (001/006)
   0.003821     - VendorID: 174c
   0.003868     - ProductID: 1153
   0.003909     - Manufacturer: unknown
   0.003949     - Product: unknown
   0.003989     - Serial Number: unknown
   0.004029     - Bus: 001
   0.004067     Trying to match device
   0.004117     Device does not match - skipping
   0.004174     Checking device (06DA/FFFF) (001/005)
   0.010156     - VendorID: 06da
   0.010204     - ProductID: ffff
   0.010245     - Manufacturer: PPC
   0.010285     - Product: HID UPS
   0.010324     - Serial Number: 716317C00120
   0.010364     - Bus: 001
   0.010403     Trying to match device
   0.010563     Device matches
   0.011565     HID descriptor length 1393
   0.033784     Report Descriptor size = 1393
   0.036523     Using subdriver: Liebert HID 0.3
   0.037062     Path: UPS.BatterySystem.Battery.BatteryID, Type: Feature, ReportID: 0x20, Offset: 0, Size: 8, Value: 1
   0.037555     Path: UPS.BatterySystem.Battery.ffff0090, Type: Feature, ReportID: 0x21, Offset: 0, Size: 8, Value: 3
   0.038061     Path: UPS.BatterySystem.Battery.PresentStatus.Present, Type: Feature, ReportID: 0x27, Offset: 0, Size: 8, Value: 1
   0.038141     Path: UPS.BatterySystem.Battery.PresentStatus.Present, Type: Input, ReportID: 0x27, Offset: 0, Size: 8, Value: 1
   0.038217     Path: UPS.BatterySystem.Battery.PresentStatus.ffff0074, Type: Feature, ReportID: 0x27, Offset: 8, Size: 8, Value: 0
   0.038292     Path: UPS.BatterySystem.Battery.PresentStatus.ffff0074, Type: Input, ReportID: 0x27, Offset: 8, Size: 8, Value: 0
   0.038801     Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 1
   0.040554     Path: UPS.BatterySystem.Battery.ffff00e3, Type: Feature, ReportID: 0xe3, Offset: 0, Size: 8, Value: 1
   0.041067     Path: UPS.BatterySystem.Battery.ffff0045, Type: Feature, ReportID: 0x25, Offset: 0, Size: 32, Value: 2.4192e+06
   0.041138     Path: UPS.BatterySystem.BatterySystemID, Type: Feature, ReportID: 0x20, Offset: 8, Size: 8, Value: 1
   0.041206     Path: UPS.BatterySystem.Charger.ChargerID, Type: Feature, ReportID: 0x20, Offset: 16, Size: 8, Value: 1
   0.041677     Path: UPS.BatterySystem.Charger.ffff0094, Type: Feature, ReportID: 0x26, Offset: 0, Size: 8, Value: 4
   0.041757     Path: UPS.BatterySystem.Charger.PresentStatus.ffff0079, Type: Feature, ReportID: 0x27, Offset: 16, Size: 8, Value: 0
   0.041832     Path: UPS.BatterySystem.Charger.PresentStatus.ffff0079, Type: Input, ReportID: 0x27, Offset: 16, Size: 8, Value: 0
   0.041905     Path: UPS.BatterySystem.Charger.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x27, Offset: 24, Size: 8, Value: 0
   0.041978     Path: UPS.BatterySystem.Charger.PresentStatus.InternalFailure, Type: Input, ReportID: 0x27, Offset: 24, Size: 8, Value: 0
   0.042052     Path: UPS.BatterySystem.Charger.PresentStatus.Used, Type: Feature, ReportID: 0x27, Offset: 32, Size: 8, Value: 1
   0.042125     Path: UPS.BatterySystem.Charger.PresentStatus.Used, Type: Input, ReportID: 0x27, Offset: 32, Size: 8, Value: 1
   0.042555     Path: UPS.Flow.[1].ConfigFrequency, Type: Feature, ReportID: 0x14, Offset: 0, Size: 8, Value: 50
   0.043060     Path: UPS.Flow.[1].ConfigVoltage, Type: Feature, ReportID: 0x15, Offset: 0, Size: 8, Value: 230
   0.043561     Path: UPS.Flow.[1].FlowID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 1
   0.044061     Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 1350
   0.044141     Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x74, Offset: 16, Size: 16, Value: 1500
   0.044679     Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 50
   0.045179     Path: UPS.Flow.[4].ConfigPercentLoad, Type: Feature, ReportID: 0x16, Offset: 0, Size: 8, Value: 110
   0.045680     Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x72, Offset: 0, Size: 8, Value: 230
   0.045759     Path: UPS.Flow.[4].FlowID, Type: Feature, ReportID: 0x0b, Offset: 8, Size: 8, Value: 4
   0.047442     Path: UPS.OutletSystem.Outlet.[1].FlowID, Type: Feature, ReportID: 0x80, Offset: 0, Size: 8, Value: 4
   0.047525     Path: UPS.OutletSystem.Outlet.[1].OutletID, Type: Feature, ReportID: 0x80, Offset: 8, Size: 8, Value: 0
   0.049313     Path: UPS.OutletSystem.Outlet.[1].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 0, Size: 8, Value: 0
   0.051061     Path: UPS.OutletSystem.Outlet.[2].DelayBeforeShutdown, Type: Feature, ReportID: 0x8d, Offset: 0, Size: 32, Value: -1
   0.052811     Path: UPS.OutletSystem.Outlet.[2].DelayBeforeStartup, Type: Feature, ReportID: 0x90, Offset: 0, Size: 32, Value: -1
   0.052962     Path: UPS.OutletSystem.Outlet.[2].FlowID, Type: Feature, ReportID: 0x80, Offset: 16, Size: 8, Value: 4
   0.053053     Path: UPS.OutletSystem.Outlet.[2].OutletID, Type: Feature, ReportID: 0x80, Offset: 24, Size: 8, Value: 1
   0.053128     Path: UPS.OutletSystem.Outlet.[2].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 8, Size: 8, Value: 1
   0.054812     Path: UPS.OutletSystem.Outlet.[2].PresentStatus.SwitchOn/Off, Type: Feature, ReportID: 0x82, Offset: 0, Size: 8, Value: 1
   0.054890     Path: UPS.OutletSystem.Outlet.[2].PresentStatus.SwitchOn/Off, Type: Input, ReportID: 0x82, Offset: 0, Size: 8, Value: 1
   0.056562     Path: UPS.OutletSystem.Outlet.[2].ffff005d, Type: Feature, ReportID: 0x87, Offset: 0, Size: 32, Value: -1
   0.058313     Path: UPS.OutletSystem.Outlet.[2].ffff005e, Type: Feature, ReportID: 0x8a, Offset: 0, Size: 32, Value: 3
   0.060062     Path: UPS.OutletSystem.Outlet.[3].DelayBeforeShutdown, Type: Feature, ReportID: 0x8e, Offset: 0, Size: 32, Value: -1
   0.061811     Path: UPS.OutletSystem.Outlet.[3].DelayBeforeStartup, Type: Feature, ReportID: 0x91, Offset: 0, Size: 32, Value: -1
   0.061894     Path: UPS.OutletSystem.Outlet.[3].FlowID, Type: Feature, ReportID: 0x80, Offset: 32, Size: 8, Value: 4
   0.061974     Path: UPS.OutletSystem.Outlet.[3].OutletID, Type: Feature, ReportID: 0x80, Offset: 40, Size: 8, Value: 2
   0.062049     Path: UPS.OutletSystem.Outlet.[3].PresentStatus.Switchable, Type: Feature, ReportID: 0x81, Offset: 16, Size: 8, Value: 1
   0.062123     Path: UPS.OutletSystem.Outlet.[3].PresentStatus.SwitchOn/Off, Type: Feature, ReportID: 0x82, Offset: 8, Size: 8, Value: 1
   0.062196     Path: UPS.OutletSystem.Outlet.[3].PresentStatus.SwitchOn/Off, Type: Input, ReportID: 0x82, Offset: 8, Size: 8, Value: 1
   0.063941     Path: UPS.OutletSystem.Outlet.[3].ffff005d, Type: Feature, ReportID: 0x88, Offset: 0, Size: 32, Value: -1
   0.065689     Path: UPS.OutletSystem.Outlet.[3].ffff005e, Type: Feature, ReportID: 0x8b, Offset: 0, Size: 32, Value: 6
   0.067425     Path: UPS.OutletSystem.ffff00c0, Type: Feature, ReportID: 0xc0, Offset: 0, Size: 8, Value: 2
   0.067501     Path: UPS.OutletSystem.OutletSystemID, Type: Feature, ReportID: 0x80, Offset: 48, Size: 8, Value: 1
   0.069178     Path: UPS.PowerConverter.ffff0041, Type: Feature, ReportID: 0x4a, Offset: 0, Size: 8, Value: 1
   0.069683     Path: UPS.PowerConverter.Input.[1].ffff0043, Type: Feature, ReportID: 0x73, Offset: 0, Size: 8, Value: 1
   0.071432     Path: UPS.PowerConverter.Input.[1].ffff0094, Type: Feature, ReportID: 0xc1, Offset: 0, Size: 8, Value: 0
   0.071934     Path: UPS.PowerConverter.Input.[1].FlowID, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 1
   0.072436     Path: UPS.PowerConverter.Input.[1].Frequency, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 50
   0.072515     Path: UPS.PowerConverter.Input.[1].InputID, Type: Feature, ReportID: 0x30, Offset: 8, Size: 8, Value: 1
   0.074190     Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Feature, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
   0.074274     Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Input, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
   0.074348     Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Feature, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
   0.074421     Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Input, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
   0.074941     Path: UPS.PowerConverter.Input.[1].PresentStatus.FrequencyOutOfRange, Type: Feature, ReportID: 0x32, Offset: 0, Size: 8, Value: 0
   0.075021     Path: UPS.PowerConverter.Input.[1].PresentStatus.FrequencyOutOfRange, Type: Input, ReportID: 0x32, Offset: 0, Size: 8, Value: 0
   0.075127     Path: UPS.PowerConverter.Input.[1].PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x32, Offset: 8, Size: 8, Value: 0
   0.075203     Path: UPS.PowerConverter.Input.[1].PresentStatus.VoltageOutOfRange, Type: Input, ReportID: 0x32, Offset: 8, Size: 8, Value: 0
   0.075280     Path: UPS.PowerConverter.Input.[1].PresentStatus.ffff0078, Type: Feature, ReportID: 0x32, Offset: 16, Size: 8, Value: 0
   0.075356     Path: UPS.PowerConverter.Input.[1].PresentStatus.ffff0078, Type: Input, ReportID: 0x32, Offset: 16, Size: 8, Value: 0
   0.075432     Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 16, Size: 16, Value: 229
   0.075936     Path: UPS.PowerConverter.Input.[3].ffff0046, Type: Feature, ReportID: 0x39, Offset: 0, Size: 8, Value: 0
   0.076014     Path: UPS.PowerConverter.Input.[3].FlowID, Type: Feature, ReportID: 0x30, Offset: 16, Size: 8, Value: 3
   0.076089     Path: UPS.PowerConverter.Input.[3].InputID, Type: Feature, ReportID: 0x30, Offset: 24, Size: 8, Value: 3
   0.076572     Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Feature, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
   0.076648     Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Input, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
   0.077185     Path: UPS.PowerConverter.Input.[3].ffff0047, Type: Feature, ReportID: 0x3a, Offset: 0, Size: 8, Value: 1
   0.077690     Path: UPS.PowerConverter.ffff0014.ffff0015, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 1
   0.078188     Path: UPS.PowerConverter.ffff0014.PresentStatus.Used, Type: Feature, ReportID: 0x41, Offset: 0, Size: 8, Value: 0
   0.078263     Path: UPS.PowerConverter.ffff0014.PresentStatus.Used, Type: Input, ReportID: 0x41, Offset: 0, Size: 8, Value: 0
   0.079939     Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0074, Type: Feature, ReportID: 0x3e, Offset: 0, Size: 8, Value: 0
   0.080016     Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0074, Type: Input, ReportID: 0x3e, Offset: 0, Size: 8, Value: 0
   0.080089     Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0075, Type: Feature, ReportID: 0x3e, Offset: 8, Size: 8, Value: 0
   0.080162     Path: UPS.PowerConverter.ffff0014.PresentStatus.ffff0075, Type: Input, ReportID: 0x3e, Offset: 8, Size: 8, Value: 0
   0.080817     Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x42, Offset: 0, Size: 16, Value: 192
   0.080901     Path: UPS.PowerConverter.Output.ApparentPower, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 289
   0.080971     Path: UPS.PowerConverter.Output.FlowID, Type: Feature, ReportID: 0x40, Offset: 8, Size: 8, Value: 4
   0.081048     Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x42, Offset: 32, Size: 16, Value: 50
   0.081560     Path: UPS.PowerConverter.Output.ffff0053, Type: Feature, ReportID: 0x4d, Offset: 0, Size: 16, Value: 243
   0.082059     Path: UPS.PowerConverter.Output.HighVoltageTransfer, Type: Feature, ReportID: 0x48, Offset: 0, Size: 16, Value: 276
   0.082559     Path: UPS.PowerConverter.Output.ffff0050, Type: Feature, ReportID: 0x4e, Offset: 0, Size: 16, Value: 207
   0.083064     Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 184
   0.083145     Path: UPS.PowerConverter.Output.OutputID, Type: Feature, ReportID: 0x40, Offset: 16, Size: 8, Value: 1
   0.083684     Path: UPS.PowerConverter.Output.PresentStatus.ffff004a, Type: Feature, ReportID: 0x49, Offset: 0, Size: 8, Value: 0
   0.083759     Path: UPS.PowerConverter.Output.PresentStatus.ffff004a, Type: Input, ReportID: 0x49, Offset: 0, Size: 8, Value: 0
   0.083837     Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 48, Size: 16, Value: 228
   0.083904     Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x40, Offset: 24, Size: 8, Value: 1
   0.084428     Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   0.084933     Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 8, Value: 1
   0.085033     Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x0c, Offset: 8, Size: 8, Value: 2
   0.085553     Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 36
   0.085629     Path: UPS.PowerSummary.ffff0095, Type: Feature, ReportID: 0x0b, Offset: 16, Size: 8, Value: 0
   0.086056     Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: -1
   0.086557     Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: -1
   0.086633     Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x0c, Offset: 16, Size: 8, Value: 100
   0.086704     Path: UPS.PowerSummary.FlowID, Type: Feature, ReportID: 0x0b, Offset: 24, Size: 8, Value: 4
   0.086773     Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x0c, Offset: 24, Size: 8, Value: 100
   0.087312     Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
   0.087389     Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x10, Offset: 8, Size: 8, Value: 1
   0.087464     Path: UPS.PowerSummary.ffff00f0, Type: Feature, ReportID: 0x10, Offset: 16, Size: 8, Value: 3
   0.087536     Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x10, Offset: 24, Size: 8, Value: 2
   0.087609     Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x10, Offset: 32, Size: 8, Value: 4
   0.087682     Path: UPS.PowerSummary.ffff00f1, Type: Feature, ReportID: 0x10, Offset: 40, Size: 8, Value: 6
   0.087756     Path: UPS.PowerSummary.ffff00f2, Type: Feature, ReportID: 0x10, Offset: 48, Size: 8, Value: 8
   0.089433     Path: UPS.PowerSummary.ffff00e2, Type: Feature, ReportID: 0xe2, Offset: 0, Size: 8, Value: 12
   0.089936     Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 19
   0.090010     Path: UPS.PowerSummary.PowerSummaryID, Type: Feature, ReportID: 0x0b, Offset: 32, Size: 8, Value: 1
   0.091680     Path: UPS.PowerSummary.ffff0094, Type: Feature, ReportID: 0xe1, Offset: 0, Size: 8, Value: 3
   0.092187     Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   0.092265     Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   0.092338     Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   0.092410     Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   0.092482     Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   0.092554     Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   0.092625     Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   0.092696     Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   0.093187     Path: UPS.PowerSummary.PresentStatus.ffff0077, Type: Feature, ReportID: 0x03, Offset: 0, Size: 8, Value: 0
   0.093265     Path: UPS.PowerSummary.PresentStatus.ffff0077, Type: Input, ReportID: 0x03, Offset: 0, Size: 8, Value: 0
   0.093337     Path: UPS.PowerSummary.PresentStatus.Good, Type: Feature, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
   0.093408     Path: UPS.PowerSummary.PresentStatus.Good, Type: Input, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
   0.093933     Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 0
   0.094006     Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x02, Offset: 0, Size: 8, Value: 0
   0.094075     Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Feature, ReportID: 0x02, Offset: 8, Size: 8, Value: 0
   0.094143     Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x02, Offset: 8, Size: 8, Value: 0
   0.094237     Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
   0.094306     Path: UPS.PowerSummary.PresentStatus.Overload, Type: Input, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
   0.094373     Path: UPS.PowerSummary.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
   0.094439     Path: UPS.PowerSummary.PresentStatus.OverTemperature, Type: Input, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
   0.094936     Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   0.095013     Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   0.095087     Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
   0.095160     Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
   0.095234     Path: UPS.PowerSummary.Temperature, Type: Feature, ReportID: 0x07, Offset: 8, Size: 16, Value: 298.9
   0.095306     Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 24, Size: 16, Value: 41.1
   0.097043     libusb_get_report: error sending control message: Operation not permitted
   0.097114     Can't retrieve Report f0: Operation not permitted
   0.097177     Path: UPS.ffff0010.[1].ffff00f0, Type: Feature, ReportID: 0xf0, Offset: 0, Size: 8
   0.098916     libusb_get_report: error sending control message: Operation not permitted
   0.098972     Can't retrieve Report f1: Operation not permitted
   0.099032     Path: UPS.ffff0010.[1].ffff00f1, Type: Feature, ReportID: 0xf1, Offset: 0, Size: 8
   0.099561     Path: UPS.ffff0010.[1].ffff00ff, Type: Feature, ReportID: 0xff, Offset: 0, Size: 8, Value: 0
   0.099680     Report descriptor retrieved (Reportlen = 1393)
   0.099724     Found HID device
   0.099767     Detected a UPS: PPC/HID UPS
   0.099898     Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 24, Size: 16, Value: 41.1
   0.099997     Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 36
   0.100112     Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   0.100225     Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 32, Value: 2987
   0.100339     Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
   0.101340     Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 19
   0.101455     Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   0.101551     Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   0.101646     Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   0.101739     Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   0.101824     Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x02, Offset: 16, Size: 8, Value: 0
   0.101898     find_nut_info: unknown info type: load.off.delay
   0.101942     find_nut_info: unknown info type: load.on.delay
   0.101983     find_nut_info: unknown info type: load.off.delay
   0.102055     upsdrv_initinfo...
   0.102118     upsdrv_updateinfo...
   0.184313     Got 2 HID objects...
   0.184405     Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   0.184503     Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 32, Value: 2927
   0.184576     Quick update...
   0.184642     Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   0.184707     Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   0.184772     Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   0.184872     Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   0.185113     dstate_init: sock /var/run/nut/usbhid-ups-pokoje open on fd 5
   0.185200     upsdrv_updateinfo...
   0.435446     libusb_get_interrupt: Connection timed out
   0.435542     Got 0 HID objects...
   0.435586     Quick update...
   0.435656     Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   0.435724     Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   0.435790     Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   0.435855     Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   2.187000     upsdrv_updateinfo...

goldie83 avatar Jul 03 '18 16:07 goldie83

I also own this device. In the current git-version the MGE-HID driver claims this vendor/product id and actually delivers more values (eg support for the outlets) and command support:

upsc pw
Init SSL without certificate database
battery.charge: 100
battery.charger.status: floating
battery.energysave: no
battery.runtime: 6244
battery.type: PbAc
device.mfr: PPC
device.model: HID UPS Sinewave 1500VA UPS
device.serial: 716318C00018    
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 15
driver.parameter.port: auto
driver.parameter.productid: ffff
driver.parameter.synchronous: no
driver.parameter.vendorid: 06da
driver.version: 2.7.4-708-g241848c3
driver.version.data: MGE HID 1.44
driver.version.internal: 0.43
input.frequency: 50.0
input.frequency.nominal: 50
input.transfer.boost.low: 207
input.transfer.high: 276
input.transfer.low: 184
input.transfer.trim.high: 243
input.voltage: 233.0
input.voltage.nominal: 230
outlet.1.delay.shutdown: 2147483647
outlet.1.delay.start: 3
outlet.1.desc: PowerShare Outlet 1
outlet.1.id: 1
outlet.1.status: on
outlet.1.switchable: yes
outlet.2.delay.shutdown: 2147483647
outlet.2.delay.start: 6
outlet.2.desc: PowerShare Outlet 2
outlet.2.id: 2
outlet.2.status: on
outlet.2.switchable: yes
outlet.desc: Main Outlet
outlet.id: 0
outlet.switchable: no
output.frequency: 50.0
output.frequency.nominal: 50
output.voltage: 233.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.firmware: 05649-0499
ups.load: 10
ups.load.high: 110
ups.mfr: PPC
ups.model: HID UPS Sinewave 1500VA UPS
ups.power: 152
ups.power.nominal: 1500
ups.productid: ffff
ups.realpower: 96
ups.realpower.nominal: 1350
ups.serial: 716318C00018    
ups.start.auto: yes
ups.start.battery: yes
ups.status: OL CHRG
ups.temperature: 34.0
ups.test.interval: 2419200
ups.test.result: Done and passed
ups.timer.shutdown: -1
ups.timer.start: -1
ups.type: offline / line interactive
ups.vendorid: 06da

BUT: the online/onbatt status fluctuates:

root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OL CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OB CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OB CHRG
root@pihole:~/nut# upsc pw ups.status
Init SSL without certificate database
OL CHRG

During "quick poll" all is good, only a full-hid-scan sets it as offline.

The issue is, that the firmware of this device sends a "UPS.PowerConverter.Input.[3].PresentStatus.Used" during normal operations (AC present) and the original MGE sees this as on bat:

1201.398937	[D2] Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
1201.398985	[D5] hu_find_infoval: found online (value: 1)
1201.399027	[D5] process_boolean_info: online
1201.399065	[D4] Entering libusb_get_report
1201.399603	[D3] Report[get]: (2 bytes) => 3b 01
1201.399659	[D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.399704	[D5] Unit = 00000000, UnitExp = 0
1201.399740	[D5] Exponent = 0
1201.399784	[D2] Path: UPS.PowerConverter.Input.[3].PresentStatus.Used, Type: Feature, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1
1201.399830	[D5] hu_find_infoval: found !online (value: 1)
1201.399870	[D5] process_boolean_info: !online
1201.399925	[D3] Report[buf]: (6 bytes) => 01 01 00 01 00 01
1201.399968	[D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.400009	[D5] Unit = 00000000, UnitExp = 0
1201.400048	[D5] Exponent = 0
1201.400091	[D2] Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
1201.400135	[D5] process_boolean_info: !dischrg
1201.400190	[D3] Report[buf]: (6 bytes) => 01 01 00 01 00 01
1201.400233	[D5] PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
1201.400276	[D5] Unit = 00000000, UnitExp = 0
1201.400314	[D5] Exponent = 0

Can mge-hid.c be changed so that the "UPS.PowerConverter.Input.[3].PresentStatus.Used" is NOT applied/considered as offline for the specific manufacturer/model ups.mfr: PPC ups.model: HID UPS Sinewave 1500VA UPS ?

I could test, but lack coding skills to do that on my own.

mdillmann avatar Jul 08 '19 07:07 mdillmann

I got the same problem as @mdillmann with PowerWalker VI 1000 ERT HID. onbatt and online status are fluctuating. Not possible to send notifications.

I tried to filter the events with upssched timer but no luck because when it is onbatt, sometimes it reports an online event between.

Is there a workaround or can we excpect a fix here?

Sep 07 14:05:58 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:06:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:06:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:06:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:06:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:07:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:07:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:07:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:07:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:08:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:08:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:08:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:08:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:09:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:09:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:09:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:09:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:10:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:10:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:10:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:10:53 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:11:13 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:11:23 pve upsmon[256568]: UPS powerwalker@localhost on line power
Sep 07 14:11:43 pve upsmon[256568]: UPS powerwalker@localhost on battery
Sep 07 14:11:53 pve upsmon[256568]: UPS powerwalker@localhost on line power

cuthulino avatar Sep 07 '22 12:09 cuthulino

@cuthulino : just in case, which version of NUT are you running? If it is a packaged one (e.g. old v2.7.4) then probably no fix is expected until distros update their recipes to deliver a newer NUT release. What you have packaged - is set in stone. If you're (open to) running a custom build, there's a chance :)

As I re-read this issue (and thanks to @mdillmann for analysis above), it sounded reminiscent of onlinedischarge feature added before NUT v2.8.0 (hence the question - maybe the new release does happen to address this behavior?), although upon closer reading into the code of that change at #811 and #1359 - maybe it does not and just is similar... similar enough to propose another toggle to either completely disable looking at that report as @mdillmann proposed, or to ignore !online from UPS.PowerConverter.Input.[3].PresentStatus.Used if UPS.PowerSummary.PresentStatus.ACPresent says we are online (and for good measure, if we are not discharging at the moment).

CC @aquette about whether/how this can be done in a sane manner? Move from mge_onbatt_info static mapping to a function like eaton_converter_online_fun from eaton_converter_online_info dynamic mapping, that would consider recent (timed to not expire) readings from those several data sources, and/or the user toggle to ignore some of the data sources?

Also generally, why would it flip? Is it a firmware bug to nag the vendor about, or does it reflect inner workings of that UPS way too honestly (e.g. some line-interactive "Power Converter" device really going "offline" so the UPS load is fed by the wall power directly, and this intimate knowledge is misinterpreted by NUT driver)?

jimklimov avatar Sep 08 '22 10:09 jimklimov

@mdillmann @cuthulino : Also as for a local PoC fix, you can try to comment away (move under nearby #if 0) the mapping line https://github.com/networkupstools/nut/blob/master/drivers/mge-hid.c#L1251 and rebuild NUT locally. It should then ignore/not-query that information, so we can see if that ignorance generally helps with these devices.

Another idea is to swap the order of two neighboring lines, placing "ACPresent" after "Input[3]...Used" - so if both are served by the device, the "ACPresent" takes precedence (would be queried last), I suppose... Usually with named data points (not like "BOOL" here) is the opposite - the first successful reading wins, so we strive to list most relevant/precise/... mappings on top and fallbacks in the end.

jimklimov avatar Sep 08 '22 10:09 jimklimov

And as a side note: curious how many mappings apply to "PowerWalker VI" series - here different versions of NUT covered it with Liebert and MGE mapping support, and in #1512 the device has a completely different vendor and product ID and so gets covered as a CyberPower (CPS) unit... There it is allegedly "PowerWalker VI 500 R1U" with a manufacturer field saying "1" :)

jimklimov avatar Sep 08 '22 10:09 jimklimov

@jimklimov you are right. I am really running the old 2.7.4 from the packages.

I will try the 2.8.0 in the next days and report back, if the error persists.

cuthulino avatar Sep 09 '22 10:09 cuthulino

@jimklimov I have the same Problem with 2.8.0

warp735 avatar May 31 '23 10:05 warp735

@warp735 : Same model? NUT 2.8.0 release or more recent (e.g. custom build from github master)?

jimklimov avatar May 31 '23 11:05 jimklimov

@jimklimov sorry, just saw that it's still 2.7 (use Unraid) Yes, it's the same model and the same error.

warp735 avatar May 31 '23 11:05 warp735

@warp735 has since confirmed his VI 1000 RT HID working with NUT 2.8.0 on UNRAID see https://forums.unraid.net/topic/60217-plugin-nut-v2-network-ups-tools/?do=findComment&comment=1288104

desertwitch avatar Jul 26 '23 12:07 desertwitch

I just upgraded to bookworm and can confirm it is working with the 1500 hid.

cuthulino avatar Jul 26 '23 14:07 cuthulino