PICs failures caused by out of date BACnet core module
Attempting to resolve a pics test failure and why certain objects could be seen by other BACnet scanners and not DAQ. I found that DAQ is resolving these missing object types as "Vendor Specific." The objects in question are Characterstring, Integer Value and Positive Integer Value which were introduced in 135-2008 Addendum w (http://www.bacnetwiki.com/wiki/index.php?title=BACnet_Standard). I don't know what current standard the BACnet core module is at but it is definitely behind in supported objects.