Charging doesn't start while there is a lot of PV surplus
Describe the bug
SMA 4kW on Phase 2 Generating 18A of solar Alfen, Alfen L1 is connected to Phase 2, Alfen L2 is connected to Phase 3, Alfen L3 is connected to Phase 1 EVCC set to charge on 1 phase Nothing happens, huge amount of feed (more than 3kW) but EVCC does not start charging
When I turned on my airconditioning which is also connected to Phase 2, the feed in dropped and EVCC started charging. --> EVCC sees the 18A of feed in as loadbalanced used amps I think
Logging: around 13:58 charging started
Steps to reproduce
...
Configuration details
circuits:
- name: AutomaatNetaansluiting
maxCurrent: 20
maxPower: 4150 #max peak on grid
meter: HuisMeter
parent:
- name: AutomaatLaadpaalVoortuin
maxCurrent: 32
maxPower: 11000 #11kW
meter:
parent: AutomaatNetaansluiting
- name: AutomaatLaadpaalOprit
maxCurrent: 10
maxPower: 2400 #11kW
meter:
parent: AutomaatNetaansluiting
loadpoints:
- title: Voortuin # display name for UI
charger: ChargingPointAlfen # Wallbox Referenz
circuit: AutomaatLaadpaalVoortuin
mode: minpv # charge mode (off, now, minpv, pv)
guardduration: 2m
enable:
threshold: 0
delay: 10s
disable:
threshold: 0 # maximum import power (W)
delay: 5m
- title: Oprit
charger: wallbox1
circuit: AutomaatLaadpaalOprit
mode: pv
Log details
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:36 power: -4354.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:36 current: 15A
[site ] DEBUG 2024/08/28 13:54:36 pv power: 5198W
[site ] DEBUG 2024/08/28 13:54:36 grid meter: -4355W
[site ] DEBUG 2024/08/28 13:54:37 grid powers: [209 -3674 -889]W
[site ] DEBUG 2024/08/28 13:54:38 grid currents: [1.44 -15 -3.79]A
[site ] DEBUG 2024/08/28 13:54:38 site power: -4345W
[lp-1 ] DEBUG 2024/08/28 13:54:38 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:54:38 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:54:38 pv charge current: 18.9A = 0A + 18.9A (-4345W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:38 validate current: 15A + (0A -> 18.9A) > 20A capped at 5.05A
[site ] DEBUG 2024/08/28 13:54:39 ----
[lp-1 ] DEBUG 2024/08/28 13:54:39 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:54:39 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:54:39 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:54:39 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:39 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:39 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:39 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:39 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:40 power: -4354.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:40 current: 15A
[site ] DEBUG 2024/08/28 13:54:40 pv power: 5198W
[site ] DEBUG 2024/08/28 13:54:40 grid meter: -4348W
[site ] DEBUG 2024/08/28 13:54:41 grid powers: [210 -3674 -884]W
[site ] DEBUG 2024/08/28 13:54:41 grid currents: [1.44 -14.9 -3.69]A
[site ] DEBUG 2024/08/28 13:54:41 site power: -4338W
[lp-2 ] DEBUG 2024/08/28 13:54:41 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:54:41 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:54:41 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:54:41 charger status: A
[lp-2 ] ERROR 2024/08/28 13:54:41 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:54:44 ----
[lp-1 ] DEBUG 2024/08/28 13:54:44 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:54:44 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:54:44 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:54:44 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:44 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:44 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:44 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:44 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:45 power: -4264.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:45 current: 15A
[site ] DEBUG 2024/08/28 13:54:45 pv power: 5192W
[site ] DEBUG 2024/08/28 13:54:45 grid meter: -4289W
[site ] DEBUG 2024/08/28 13:54:46 grid powers: [208 -3671 -835]W
[site ] DEBUG 2024/08/28 13:54:47 grid currents: [1.45 -15 -3.59]A
[site ] DEBUG 2024/08/28 13:54:47 site power: -4279W
[lp-1 ] DEBUG 2024/08/28 13:54:47 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:54:47 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:54:47 pv charge current: 18.6A = 0A + 18.6A (-4279W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:54:47 validate current: 15A + (0A -> 18.6A) > 20A capped at 5.02A
[site ] DEBUG 2024/08/28 13:54:49 ----
[lp-1 ] DEBUG 2024/08/28 13:54:49 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:54:49 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:54:49 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:54:49 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:49 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:54:49 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:49 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:54:49 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:05 power: -4284W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:05 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:05 pv power: 5201W
[site ] DEBUG 2024/08/28 13:55:06 grid meter: -4282W
[site ] DEBUG 2024/08/28 13:55:06 grid powers: [208 -3672 -762]W
[site ] DEBUG 2024/08/28 13:55:07 grid currents: [1.44 -14.9 -3.37]A
[site ] DEBUG 2024/08/28 13:55:07 site power: -4272W
[lp-2 ] DEBUG 2024/08/28 13:55:07 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:55:07 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:55:07 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:55:07 charger status: A
[lp-2 ] ERROR 2024/08/28 13:55:07 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:55:07 ----
[lp-1 ] DEBUG 2024/08/28 13:55:07 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:07 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:07 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:07 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:07 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:07 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:07 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:07 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:08 power: -4187.2W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:08 current: 14.8A
[site ] DEBUG 2024/08/28 13:55:08 pv power: 5201W
[site ] DEBUG 2024/08/28 13:55:08 grid meter: -4235W
[site ] DEBUG 2024/08/28 13:55:09 grid powers: [208 -3660 -796]W
[site ] DEBUG 2024/08/28 13:55:09 grid currents: [1.44 -14.9 -3.51]A
[site ] DEBUG 2024/08/28 13:55:09 site power: -4225W
[lp-1 ] DEBUG 2024/08/28 13:55:09 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:55:10 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:55:10 pv charge current: 18.4A = 0A + 18.4A (-4225W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:10 validate current: 14.8A + (0A -> 18.4A) > 20A capped at 5.16A
[site ] DEBUG 2024/08/28 13:55:10 ----
[lp-1 ] DEBUG 2024/08/28 13:55:10 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:10 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:10 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:10 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:10 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:10 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:10 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:10 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:10 power: -4263.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:10 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:10 pv power: 5210W
[site ] DEBUG 2024/08/28 13:55:10 grid meter: -4258W
[site ] DEBUG 2024/08/28 13:55:11 grid powers: [209 -3676 -770]W
[site ] DEBUG 2024/08/28 13:55:11 grid currents: [1.45 -14.9 -3.46]A
[site ] DEBUG 2024/08/28 13:55:12 site power: -4248W
[lp-2 ] DEBUG 2024/08/28 13:55:12 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:55:12 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:55:12 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:55:12 charger status: A
[lp-2 ] ERROR 2024/08/28 13:55:12 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:55:14 ----
[lp-1 ] DEBUG 2024/08/28 13:55:14 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:14 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:14 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:14 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:14 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:14 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:14 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:14 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:15 power: -4344.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:15 current: 15A
[site ] DEBUG 2024/08/28 13:55:15 pv power: 5211W
[site ] DEBUG 2024/08/28 13:55:15 grid meter: -4338W
[site ] DEBUG 2024/08/28 13:55:16 grid powers: [209 -3673 -881]W
[site ] DEBUG 2024/08/28 13:55:16 grid currents: [1.44 -14.9 -3.76]A
[site ] DEBUG 2024/08/28 13:55:16 site power: -4328W
[lp-1 ] DEBUG 2024/08/28 13:55:16 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:55:17 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:55:17 pv charge current: 18.8A = 0A + 18.8A (-4328W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:17 validate current: 15A + (0A -> 18.8A) > 20A capped at 5.05A
[site ] DEBUG 2024/08/28 13:55:19 ----
[lp-1 ] DEBUG 2024/08/28 13:55:19 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:19 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:19 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:19 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:19 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:19 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:19 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:19 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:20 power: -4344.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:20 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:20 pv power: 5219W
[site ] DEBUG 2024/08/28 13:55:21 grid meter: -4360W
[site ] DEBUG 2024/08/28 13:55:21 grid powers: [209 -3675 -857]W
[site ] DEBUG 2024/08/28 13:55:22 grid currents: [1.44 -15 -3.64]A
[site ] DEBUG 2024/08/28 13:55:22 site power: -4350W
[lp-2 ] DEBUG 2024/08/28 13:55:22 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:55:22 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:55:22 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:55:22 charger status: A
[lp-2 ] ERROR 2024/08/28 13:55:22 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:55:24 ----
[lp-1 ] DEBUG 2024/08/28 13:55:24 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:24 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:24 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:24 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:24 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:24 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:24 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:24 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:25 power: -4302.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:25 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:25 pv power: 5219W
[site ] DEBUG 2024/08/28 13:55:25 grid meter: -4304W
[site ] DEBUG 2024/08/28 13:55:26 grid powers: [212 -3673 -868]W
[site ] DEBUG 2024/08/28 13:55:26 grid currents: [1.46 -14.9 -3.62]A
[site ] DEBUG 2024/08/28 13:55:26 site power: -4294W
[lp-1 ] DEBUG 2024/08/28 13:55:26 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:55:27 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:55:27 pv charge current: 18.7A = 0A + 18.7A (-4294W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:27 validate current: 14.9A + (0A -> 18.7A) > 20A capped at 5.06A
[site ] DEBUG 2024/08/28 13:55:29 ----
[lp-1 ] DEBUG 2024/08/28 13:55:29 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:29 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:29 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:29 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:29 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:29 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:29 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:29 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:45 power: -4368.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:45 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:45 pv power: 5219W
[site ] DEBUG 2024/08/28 13:55:46 grid meter: -4341W
[site ] DEBUG 2024/08/28 13:55:47 grid powers: [208 -3674 -876]W
[site ] DEBUG 2024/08/28 13:55:49 grid currents: [1.44 -14.9 -3.85]A
[site ] DEBUG 2024/08/28 13:55:50 site power: -4331W
[lp-2 ] DEBUG 2024/08/28 13:55:50 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:55:50 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:55:50 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:55:50 charger status: A
[lp-2 ] ERROR 2024/08/28 13:55:50 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:55:50 ----
[lp-1 ] DEBUG 2024/08/28 13:55:51 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:51 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:51 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:51 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:51 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:51 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:51 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:51 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:52 power: -4326.6W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:52 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:52 pv power: 5222W
[site ] DEBUG 2024/08/28 13:55:53 grid meter: -4370W
[site ] DEBUG 2024/08/28 13:55:54 grid powers: [208 -3671 -885]W
[site ] DEBUG 2024/08/28 13:55:55 grid currents: [1.46 -14.9 -3.82]A
[site ] DEBUG 2024/08/28 13:55:55 site power: -4360W
[lp-1 ] DEBUG 2024/08/28 13:55:55 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:55:55 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:55:55 pv charge current: 19A = 0A + 19A (-4360W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:55 validate current: 14.9A + (0A -> 19A) > 20A capped at 5.07A
[site ] DEBUG 2024/08/28 13:55:55 ----
[lp-1 ] DEBUG 2024/08/28 13:55:56 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:56 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:56 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:56 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:56 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:56 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:56 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:56 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:56 power: -4378.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:55:56 current: 14.9A
[site ] DEBUG 2024/08/28 13:55:56 pv power: 5228W
[site ] DEBUG 2024/08/28 13:55:56 grid meter: -4380W
[site ] DEBUG 2024/08/28 13:55:57 grid powers: [209 -3675 -910]W
[site ] DEBUG 2024/08/28 13:55:57 grid currents: [1.45 -14.9 -3.85]A
[site ] DEBUG 2024/08/28 13:55:58 site power: -4370W
[lp-2 ] DEBUG 2024/08/28 13:55:58 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:55:58 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:55:58 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:55:58 charger status: A
[lp-2 ] ERROR 2024/08/28 13:55:58 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:55:59 ----
[lp-1 ] DEBUG 2024/08/28 13:55:59 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:55:59 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:55:59 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:55:59 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:59 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:55:59 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:59 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:55:59 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:00 power: -4372.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:00 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:00 pv power: 5229W
[site ] DEBUG 2024/08/28 13:56:01 grid meter: -4379W
[site ] DEBUG 2024/08/28 13:56:02 grid powers: [209 -3672 -903]W
[site ] DEBUG 2024/08/28 13:56:04 grid currents: [1.45 -14.9 -3.75]A
[site ] DEBUG 2024/08/28 13:56:05 site power: -4369W
[lp-1 ] DEBUG 2024/08/28 13:56:05 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:05 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:05 pv charge current: 19A = 0A + 19A (-4369W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:05 validate current: 14.9A + (0A -> 19A) > 20A capped at 5.08A
[site ] DEBUG 2024/08/28 13:56:05 ----
[lp-1 ] DEBUG 2024/08/28 13:56:05 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:06 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:06 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:06 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:06 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:06 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:06 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:06 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:07 power: -4325.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:07 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:07 pv power: 5230W
[site ] DEBUG 2024/08/28 13:56:07 grid meter: -4310W
[site ] DEBUG 2024/08/28 13:56:08 grid powers: [213 -3675 -910]W
[site ] DEBUG 2024/08/28 13:56:08 grid currents: [1.44 -14.9 -3.87]A
[site ] DEBUG 2024/08/28 13:56:09 site power: -4300W
[lp-2 ] DEBUG 2024/08/28 13:56:09 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:09 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:09 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:09 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:09 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:09 ----
[lp-1 ] DEBUG 2024/08/28 13:56:09 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:09 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:09 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:09 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:09 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:09 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:09 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:09 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:10 power: -4351.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:10 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:10 pv power: 5237W
[site ] DEBUG 2024/08/28 13:56:11 grid meter: -4380W
[site ] DEBUG 2024/08/28 13:56:12 grid powers: [212 -3677 -911]W
[site ] DEBUG 2024/08/28 13:56:12 grid currents: [1.45 -14.9 -3.79]A
[site ] DEBUG 2024/08/28 13:56:13 site power: -4370W
[lp-1 ] DEBUG 2024/08/28 13:56:13 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:13 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:13 pv charge current: 19A = 0A + 19A (-4370W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:13 validate current: 14.9A + (0A -> 19A) > 20A capped at 5.07A
[site ] DEBUG 2024/08/28 13:56:14 ----
[lp-1 ] DEBUG 2024/08/28 13:56:14 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:14 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:14 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:14 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:14 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:14 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:14 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:14 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:15 power: -4345.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:15 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:15 pv power: 5237W
[site ] DEBUG 2024/08/28 13:56:16 grid meter: -4360W
[site ] DEBUG 2024/08/28 13:56:17 grid powers: [212 -3660 -903]W
[site ] DEBUG 2024/08/28 13:56:18 grid currents: [1.46 -14.9 -3.75]A
[site ] DEBUG 2024/08/28 13:56:20 site power: -4350W
[lp-2 ] DEBUG 2024/08/28 13:56:20 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:20 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:20 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:20 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:20 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:20 ----
[lp-1 ] DEBUG 2024/08/28 13:56:20 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:20 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:20 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:20 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:20 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:20 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:20 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:20 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:22 power: -4347W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:22 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:22 pv power: 5238W
[site ] DEBUG 2024/08/28 13:56:22 grid meter: -4348W
[site ] DEBUG 2024/08/28 13:56:23 grid powers: [211 -3674 -888]W
[site ] DEBUG 2024/08/28 13:56:24 grid currents: [1.45 -14.9 -3.79]A
[site ] DEBUG 2024/08/28 13:56:25 site power: -4338W
[lp-1 ] DEBUG 2024/08/28 13:56:25 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:25 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:25 pv charge current: 18.9A = 0A + 18.9A (-4338W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:25 validate current: 14.8A + (0A -> 18.9A) > 20A capped at 5.16A
[site ] DEBUG 2024/08/28 13:56:25 ----
[lp-1 ] DEBUG 2024/08/28 13:56:25 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:25 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:25 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:25 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:25 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:25 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:25 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:25 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:26 power: -4357.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:26 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:26 pv power: 5233W
[site ] DEBUG 2024/08/28 13:56:27 grid meter: -4356W
[site ] DEBUG 2024/08/28 13:56:27 grid powers: [206 -3674 -877]W
[site ] DEBUG 2024/08/28 13:56:28 grid currents: [1.44 -14.8 -3.78]A
[site ] DEBUG 2024/08/28 13:56:28 site power: -4346W
[lp-2 ] DEBUG 2024/08/28 13:56:28 charge voltages: [243 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:28 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:28 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:28 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:28 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:29 ----
[lp-1 ] DEBUG 2024/08/28 13:56:29 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:29 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:29 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:29 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:29 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:29 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:29 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:29 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:30 power: -4383.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:30 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:30 pv power: 5233W
[site ] DEBUG 2024/08/28 13:56:30 grid meter: -4377W
[site ] DEBUG 2024/08/28 13:56:31 grid powers: [209 -3675 -906]W
[site ] DEBUG 2024/08/28 13:56:32 grid currents: [1.44 -14.8 -3.75]A
[site ] DEBUG 2024/08/28 13:56:32 site power: -4367W
[lp-1 ] DEBUG 2024/08/28 13:56:32 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:32 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:33 pv charge current: 19A = 0A + 19A (-4367W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:33 validate current: 14.8A + (0A -> 19A) > 20A capped at 5.17A
[site ] DEBUG 2024/08/28 13:56:34 ----
[lp-1 ] DEBUG 2024/08/28 13:56:34 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:34 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:34 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:34 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:34 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:34 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:34 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:34 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:35 power: -4354.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:35 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:35 pv power: 5236W
[site ] DEBUG 2024/08/28 13:56:36 grid meter: -4338W
[site ] DEBUG 2024/08/28 13:56:37 grid powers: [208 -3677 -906]W
[site ] DEBUG 2024/08/28 13:56:37 grid currents: [1.45 -14.8 -3.83]A
[site ] DEBUG 2024/08/28 13:56:38 site power: -4328W
[lp-2 ] DEBUG 2024/08/28 13:56:38 charge voltages: [245 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:38 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:38 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:38 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:38 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:39 ----
[lp-1 ] DEBUG 2024/08/28 13:56:39 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:39 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:39 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:39 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:39 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:39 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:39 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:39 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:40 power: -4370.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:40 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:40 pv power: 5236W
[site ] DEBUG 2024/08/28 13:56:40 grid meter: -4363W
[site ] DEBUG 2024/08/28 13:56:41 grid powers: [209 -3677 -896]W
[site ] DEBUG 2024/08/28 13:56:41 grid currents: [1.44 -14.8 -3.81]A
[site ] DEBUG 2024/08/28 13:56:41 site power: -4353W
[lp-1 ] DEBUG 2024/08/28 13:56:41 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:42 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:42 pv charge current: 18.9A = 0A + 18.9A (-4353W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:42 validate current: 14.8A + (0A -> 18.9A) > 20A capped at 5.19A
[site ] DEBUG 2024/08/28 13:56:44 ----
[lp-1 ] DEBUG 2024/08/28 13:56:44 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:44 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:44 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:44 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:44 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:44 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:44 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:44 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:46 power: -4381.5W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:46 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:46 pv power: 5234W
[site ] DEBUG 2024/08/28 13:56:46 grid meter: -4376W
[site ] DEBUG 2024/08/28 13:56:47 grid powers: [209 -3671 -901]W
[site ] DEBUG 2024/08/28 13:56:48 grid currents: [1.45 -14.8 -3.86]A
[site ] DEBUG 2024/08/28 13:56:48 site power: -4366W
[lp-2 ] DEBUG 2024/08/28 13:56:48 charge voltages: [245 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:48 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:48 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:48 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:48 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:49 ----
[lp-1 ] DEBUG 2024/08/28 13:56:49 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:49 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:49 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:49 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:49 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:49 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:49 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:49 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:50 power: -4372.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:50 current: 14.8A
[site ] DEBUG 2024/08/28 13:56:50 pv power: 5235W
[site ] DEBUG 2024/08/28 13:56:51 grid meter: -4378W
[site ] DEBUG 2024/08/28 13:56:51 grid powers: [208 -3673 -908]W
[site ] DEBUG 2024/08/28 13:56:52 grid currents: [1.45 -14.8 -3.82]A
[site ] DEBUG 2024/08/28 13:56:52 site power: -4368W
[lp-1 ] DEBUG 2024/08/28 13:56:52 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:56:52 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:56:53 pv charge current: 19A = 0A + 19A (-4368W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:53 validate current: 14.8A + (0A -> 19A) > 20A capped at 5.19A
[site ] DEBUG 2024/08/28 13:56:54 ----
[lp-1 ] DEBUG 2024/08/28 13:56:54 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:54 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:54 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:54 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:54 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:54 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:54 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:54 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:55 power: -4364.9W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:56:55 current: 14.9A
[site ] DEBUG 2024/08/28 13:56:55 pv power: 5235W
[site ] DEBUG 2024/08/28 13:56:55 grid meter: -4336W
[site ] DEBUG 2024/08/28 13:56:56 grid powers: [213 -3660 -899]W
[site ] DEBUG 2024/08/28 13:56:58 grid currents: [1.45 -14.8 -3.82]A
[site ] DEBUG 2024/08/28 13:56:58 site power: -4326W
[lp-2 ] DEBUG 2024/08/28 13:56:58 charge voltages: [245 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:56:58 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:56:58 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:56:58 charger status: A
[lp-2 ] ERROR 2024/08/28 13:56:58 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:56:59 ----
[lp-1 ] DEBUG 2024/08/28 13:56:59 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:56:59 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:56:59 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:56:59 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:59 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:56:59 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:59 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:56:59 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:00 power: -4361.2W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:00 current: 14.8A
[site ] DEBUG 2024/08/28 13:57:00 pv power: 5236W
[site ] DEBUG 2024/08/28 13:57:00 grid meter: -4313W
[site ] DEBUG 2024/08/28 13:57:01 grid powers: [212 -3659 -875]W
[site ] DEBUG 2024/08/28 13:57:01 grid currents: [1.45 -14.8 -3.74]A
[site ] DEBUG 2024/08/28 13:57:02 site power: -4303W
[lp-1 ] DEBUG 2024/08/28 13:57:02 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:57:02 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:57:02 pv charge current: 18.7A = 0A + 18.7A (-4303W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:02 validate current: 14.8A + (0A -> 18.7A) > 20A capped at 5.15A
[site ] DEBUG 2024/08/28 13:57:04 ----
[lp-1 ] DEBUG 2024/08/28 13:57:04 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:04 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:04 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:04 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:04 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:04 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:04 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:04 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:05 power: -4304.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:05 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:05 pv power: 5232W
[site ] DEBUG 2024/08/28 13:57:06 grid meter: -4340W
[site ] DEBUG 2024/08/28 13:57:06 grid powers: [209 -3677 -869]W
[site ] DEBUG 2024/08/28 13:57:07 grid currents: [1.44 -14.8 -3.72]A
[site ] DEBUG 2024/08/28 13:57:07 site power: -4330W
[lp-2 ] DEBUG 2024/08/28 13:57:07 charge voltages: [245 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:57:07 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:57:07 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:57:07 charger status: A
[lp-2 ] ERROR 2024/08/28 13:57:07 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:57:09 ----
[lp-1 ] DEBUG 2024/08/28 13:57:09 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:09 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:09 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:09 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:09 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:09 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:09 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:09 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:26 power: -4301.4W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:26 current: 14.7A
[site ] DEBUG 2024/08/28 13:57:26 pv power: 5220W
[site ] DEBUG 2024/08/28 13:57:27 grid meter: -4296W
[site ] DEBUG 2024/08/28 13:57:29 grid powers: [213 -3679 -833]W
[site ] DEBUG 2024/08/28 13:57:31 grid currents: [1.45 -14.9 -3.59]A
[site ] DEBUG 2024/08/28 13:57:31 site power: -4286W
[lp-1 ] DEBUG 2024/08/28 13:57:31 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:57:31 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:57:31 pv charge current: 18.6A = 0A + 18.6A (-4286W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:31 validate current: 14.7A + (0A -> 18.6A) > 20A capped at 5.29A
[site ] DEBUG 2024/08/28 13:57:31 ----
[lp-1 ] DEBUG 2024/08/28 13:57:31 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:32 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:32 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:32 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:32 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:32 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:32 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:32 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:33 power: -4299.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:33 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:33 pv power: 5218W
[site ] DEBUG 2024/08/28 13:57:34 grid meter: -4289W
[site ] DEBUG 2024/08/28 13:57:35 grid powers: [212 -3675 -829]W
[site ] DEBUG 2024/08/28 13:57:36 grid currents: [1.44 -14.9 -3.54]A
[site ] DEBUG 2024/08/28 13:57:36 site power: -4279W
[lp-2 ] DEBUG 2024/08/28 13:57:36 charge voltages: [244 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:57:36 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:57:36 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:57:36 charger status: A
[lp-2 ] ERROR 2024/08/28 13:57:36 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:57:36 ----
[lp-1 ] DEBUG 2024/08/28 13:57:36 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:36 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:36 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:36 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:36 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:36 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:36 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:36 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:38 power: -4268.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:38 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:38 pv power: 5223W
[site ] DEBUG 2024/08/28 13:57:38 grid meter: -4269W
[site ] DEBUG 2024/08/28 13:57:39 grid powers: [214 -3671 -801]W
[site ] DEBUG 2024/08/28 13:57:40 grid currents: [1.45 -14.9 -3.52]A
[site ] DEBUG 2024/08/28 13:57:40 site power: -4259W
[lp-1 ] DEBUG 2024/08/28 13:57:41 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:57:41 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:57:41 pv charge current: 18.5A = 0A + 18.5A (-4259W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:41 validate current: 14.9A + (0A -> 18.5A) > 20A capped at 5.15A
[site ] DEBUG 2024/08/28 13:57:41 ----
[lp-1 ] DEBUG 2024/08/28 13:57:41 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:41 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:41 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:41 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:41 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:41 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:41 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:41 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:42 power: -4254.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:42 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:42 pv power: 5222W
[site ] DEBUG 2024/08/28 13:57:42 grid meter: -4260W
[site ] DEBUG 2024/08/28 13:57:45 grid powers: [213 -3676 -911]W
[site ] DEBUG 2024/08/28 13:57:46 grid currents: [1.45 -14.8 -3.9]A
[site ] DEBUG 2024/08/28 13:57:47 site power: -4250W
[lp-2 ] DEBUG 2024/08/28 13:57:47 charge voltages: [244 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:57:47 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:57:47 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:57:47 charger status: A
[lp-2 ] ERROR 2024/08/28 13:57:48 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:57:48 ----
[lp-1 ] DEBUG 2024/08/28 13:57:48 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:48 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:48 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:48 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:48 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:48 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:48 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:48 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:49 power: -4388.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:49 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:49 pv power: 5225W
[site ] DEBUG 2024/08/28 13:57:49 grid meter: -4377W
[site ] DEBUG 2024/08/28 13:57:50 grid powers: [214 -3674 -909]W
[site ] DEBUG 2024/08/28 13:57:51 grid currents: [1.45 -14.9 -3.86]A
[site ] DEBUG 2024/08/28 13:57:52 site power: -4367W
[lp-1 ] DEBUG 2024/08/28 13:57:52 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:57:52 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:57:52 pv charge current: 19A = 0A + 19A (-4367W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:52 validate current: 14.9A + (0A -> 19A) > 20A capped at 5.11A
[site ] DEBUG 2024/08/28 13:57:52 ----
[lp-1 ] DEBUG 2024/08/28 13:57:52 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:53 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:53 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:53 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:53 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:53 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:53 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:53 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:54 power: -4373.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:54 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:54 pv power: 5227W
[site ] DEBUG 2024/08/28 13:57:54 grid meter: -4379W
[site ] DEBUG 2024/08/28 13:57:55 grid powers: [212 -3677 -915]W
[site ] DEBUG 2024/08/28 13:57:56 grid currents: [1.45 -14.9 -3.88]A
[site ] DEBUG 2024/08/28 13:57:56 site power: -4369W
[lp-2 ] DEBUG 2024/08/28 13:57:56 charge voltages: [244 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:57:56 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:57:56 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:57:56 charger status: A
[lp-2 ] ERROR 2024/08/28 13:57:56 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:57:56 ----
[lp-1 ] DEBUG 2024/08/28 13:57:56 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:57:56 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:57:56 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:57:56 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:56 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:57:56 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:56 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:57:56 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:58 power: -4357.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:57:58 current: 14.9A
[site ] DEBUG 2024/08/28 13:57:58 pv power: 5225W
[site ] DEBUG 2024/08/28 13:57:59 grid meter: -4371W
[site ] DEBUG 2024/08/28 13:58:01 grid powers: [214 -3682 -901]W
[site ] DEBUG 2024/08/28 13:58:03 grid currents: [1.45 -14.8 -3.71]A
[site ] DEBUG 2024/08/28 13:58:03 site power: -4361W
[lp-1 ] DEBUG 2024/08/28 13:58:03 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:03 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:04 pv charge current: 19A = 0A + 19A (-4361W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:04 validate current: 14.9A + (0A -> 19A) > 20A capped at 5.11A
[site ] DEBUG 2024/08/28 13:58:04 ----
[lp-1 ] DEBUG 2024/08/28 13:58:04 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:04 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:04 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:04 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:04 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:04 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:04 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:04 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:05 power: -4315.2W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:05 current: 14.8A
[site ] DEBUG 2024/08/28 13:58:05 pv power: 5211W
[site ] DEBUG 2024/08/28 13:58:05 grid meter: -4318W
[site ] DEBUG 2024/08/28 13:58:06 grid powers: [212 -3674 -871]W
[site ] DEBUG 2024/08/28 13:58:07 grid currents: [1.46 -14.8 -3.72]A
[site ] DEBUG 2024/08/28 13:58:07 site power: -4308W
[lp-2 ] DEBUG 2024/08/28 13:58:07 charge voltages: [244 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:58:07 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:58:07 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:58:07 charger status: A
[lp-2 ] ERROR 2024/08/28 13:58:08 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:58:08 ----
[lp-1 ] DEBUG 2024/08/28 13:58:08 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:08 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:08 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:08 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:08 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:08 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:08 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:08 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:09 power: -4332.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:09 current: 14.8A
[site ] DEBUG 2024/08/28 13:58:09 pv power: 5217W
[site ] DEBUG 2024/08/28 13:58:09 grid meter: -4352W
[site ] DEBUG 2024/08/28 13:58:10 grid powers: [212 -3674 -856]W
[site ] DEBUG 2024/08/28 13:58:10 grid currents: [1.46 -14.8 -3.67]A
[site ] DEBUG 2024/08/28 13:58:11 site power: -4342W
[lp-1 ] DEBUG 2024/08/28 13:58:11 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:11 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:11 pv charge current: 18.9A = 0A + 18.9A (-4342W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:11 validate current: 14.8A + (0A -> 18.9A) > 20A capped at 5.21A
[site ] DEBUG 2024/08/28 13:58:11 ----
[lp-1 ] DEBUG 2024/08/28 13:58:11 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:11 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:11 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:11 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:11 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:11 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:11 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:11 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:12 power: -4341.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:12 current: 14.8A
[site ] DEBUG 2024/08/28 13:58:12 pv power: 5217W
[site ] DEBUG 2024/08/28 13:58:13 grid meter: -4360W
[site ] DEBUG 2024/08/28 13:58:15 grid powers: [214 -3680 -903]W
[site ] DEBUG 2024/08/28 13:58:17 grid currents: [1.45 -14.8 -3.84]A
[site ] DEBUG 2024/08/28 13:58:17 site power: -4350W
[lp-2 ] DEBUG 2024/08/28 13:58:17 charge voltages: [246 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:58:17 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:58:17 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:58:17 charger status: A
[lp-2 ] ERROR 2024/08/28 13:58:17 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:58:17 ----
[lp-1 ] DEBUG 2024/08/28 13:58:17 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:17 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:17 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:17 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:17 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:17 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:17 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:17 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:19 power: -4366.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:19 current: 14.8A
[site ] DEBUG 2024/08/28 13:58:19 pv power: 5216W
[site ] DEBUG 2024/08/28 13:58:19 grid meter: -4346W
[site ] DEBUG 2024/08/28 13:58:20 grid powers: [213 -3674 -905]W
[site ] DEBUG 2024/08/28 13:58:21 grid currents: [1.46 -14.7 -3.8]A
[site ] DEBUG 2024/08/28 13:58:21 site power: -4336W
[lp-1 ] DEBUG 2024/08/28 13:58:21 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:21 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:22 pv charge current: 18.9A = 0A + 18.9A (-4336W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:22 validate current: 14.8A + (0A -> 18.9A) > 20A capped at 5.21A
[site ] DEBUG 2024/08/28 13:58:22 ----
[lp-1 ] DEBUG 2024/08/28 13:58:22 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:22 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:22 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:22 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:22 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:22 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:22 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:22 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:23 power: -4328W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:23 current: 14.8A
[site ] DEBUG 2024/08/28 13:58:23 pv power: 5216W
[site ] DEBUG 2024/08/28 13:58:23 grid meter: -4275W
[site ] DEBUG 2024/08/28 13:58:23 grid powers: [212 -3649 -870]W
[site ] DEBUG 2024/08/28 13:58:24 grid currents: [1.45 -14.7 -3.59]A
[site ] DEBUG 2024/08/28 13:58:24 site power: -4265W
[lp-2 ] DEBUG 2024/08/28 13:58:24 charge voltages: [246 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:58:24 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:58:24 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:58:24 charger status: A
[lp-2 ] ERROR 2024/08/28 13:58:24 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:58:24 ----
[lp-1 ] DEBUG 2024/08/28 13:58:24 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:24 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:24 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:24 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:24 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:24 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:24 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:24 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:25 power: -4268.9W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:25 current: 14.7A
[site ] DEBUG 2024/08/28 13:58:25 pv power: 5216W
[site ] DEBUG 2024/08/28 13:58:25 grid meter: -4265W
[site ] DEBUG 2024/08/28 13:58:26 grid powers: [213 -3623 -858]W
[site ] DEBUG 2024/08/28 13:58:27 grid currents: [1.41 -14.7 -3.6]A
[site ] DEBUG 2024/08/28 13:58:27 site power: -4255W
[lp-1 ] DEBUG 2024/08/28 13:58:27 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:27 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:28 pv charge current: 18.5A = 0A + 18.5A (-4255W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:28 validate current: 14.7A + (0A -> 18.5A) > 20A capped at 5.33A
[site ] DEBUG 2024/08/28 13:58:29 ----
[lp-1 ] DEBUG 2024/08/28 13:58:29 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:29 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:29 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:29 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:29 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:29 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:29 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:29 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:30 power: -4320.9W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:30 current: 14.7A
[site ] DEBUG 2024/08/28 13:58:30 pv power: 5211W
[site ] DEBUG 2024/08/28 13:58:31 grid meter: -4302W
[site ] DEBUG 2024/08/28 13:58:32 grid powers: [211 -3657 -825]W
[site ] DEBUG 2024/08/28 13:58:32 grid currents: [1.45 -14.7 -3.81]A
[site ] DEBUG 2024/08/28 13:58:33 site power: -4292W
[lp-2 ] DEBUG 2024/08/28 13:58:33 charge voltages: [247 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:58:33 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:58:33 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:58:33 charger status: A
[lp-2 ] ERROR 2024/08/28 13:58:33 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:58:34 ----
[lp-1 ] DEBUG 2024/08/28 13:58:34 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:34 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:34 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:34 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:34 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:34 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:34 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:34 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:35 power: -4247W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:35 current: 14.3A
[site ] DEBUG 2024/08/28 13:58:35 pv power: 5215W
[site ] DEBUG 2024/08/28 13:58:36 grid meter: -4230W
[site ] DEBUG 2024/08/28 13:58:37 grid powers: [210 -3555 -896]W
[site ] DEBUG 2024/08/28 13:58:37 grid currents: [1.45 -14.4 -3.83]A
[site ] DEBUG 2024/08/28 13:58:38 site power: -4220W
[lp-1 ] DEBUG 2024/08/28 13:58:38 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:38 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:38 pv charge current: 18.3A = 0A + 18.3A (-4220W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:38 validate current: 14.3A + (0A -> 18.3A) > 20A capped at 5.67A
[site ] DEBUG 2024/08/28 13:58:39 ----
[lp-1 ] DEBUG 2024/08/28 13:58:39 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:39 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:39 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:39 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:39 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:39 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:39 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:39 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:41 power: -4112.3W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:41 current: 13.9A
[site ] DEBUG 2024/08/28 13:58:41 pv power: 5216W
[site ] DEBUG 2024/08/28 13:58:42 grid meter: -3947W
[site ] DEBUG 2024/08/28 13:58:43 grid powers: [210 -3297 -806]W
[site ] DEBUG 2024/08/28 13:58:44 grid currents: [1.44 -13.3 -3.57]A
[site ] DEBUG 2024/08/28 13:58:44 site power: -3937W
[lp-2 ] DEBUG 2024/08/28 13:58:44 charge voltages: [247 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:58:44 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:58:44 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:58:44 charger status: A
[lp-2 ] ERROR 2024/08/28 13:58:44 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:58:44 ----
[lp-1 ] DEBUG 2024/08/28 13:58:44 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:45 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:45 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:45 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:45 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:45 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:45 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:45 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:45 power: -3785.6W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:45 current: 12.8A
[site ] DEBUG 2024/08/28 13:58:45 pv power: 5218W
[site ] DEBUG 2024/08/28 13:58:46 grid meter: -3727W
[site ] DEBUG 2024/08/28 13:58:46 grid powers: [210 -3080 -844]W
[site ] DEBUG 2024/08/28 13:58:47 grid currents: [1.44 -12.4 -3.57]A
[site ] DEBUG 2024/08/28 13:58:47 site power: -3717W
[lp-1 ] DEBUG 2024/08/28 13:58:47 charge total import: 13509.130kWh
[lp-1 ] DEBUG 2024/08/28 13:58:47 charger status: B
[lp-1 ] DEBUG 2024/08/28 13:58:47 pv charge current: 16.2A = 0A + 16.2A (-3717W @ 1p)
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:58:47 validate current: 12.8A + (0A -> 16.2A) > 20A capped at 7.19A
[lp-1 ] DEBUG 2024/08/28 13:58:47 max charge current: 7.19A
[lp-1 ] DEBUG 2024/08/28 13:58:47 charger enable
[lp-1 ] DEBUG 2024/08/28 13:58:47 wake-up timer: start
[site ] DEBUG 2024/08/28 13:58:49 ----
[lp-1 ] DEBUG 2024/08/28 13:58:49 charge power: 0W
[lp-1 ] DEBUG 2024/08/28 13:58:49 charge currents: [0 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:58:49 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:58:49 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:49 power: 0W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:58:49 current: 0A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:49 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:58:49 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:59:06 power: -1570.9W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:59:06 current: 5.24A
[site ] DEBUG 2024/08/28 13:59:06 pv power: 5222W
[site ] DEBUG 2024/08/28 13:59:06 grid meter: -1597W
[site ] DEBUG 2024/08/28 13:59:08 grid powers: [211 -950 -829]W
[site ] DEBUG 2024/08/28 13:59:09 grid currents: [1.45 -5.21 -3.58]A
[site ] DEBUG 2024/08/28 13:59:10 site power: -1587W
[lp-2 ] DEBUG 2024/08/28 13:59:10 charge voltages: [245 0 0]V
[lp-2 ] DEBUG 2024/08/28 13:59:10 detected connected phases: 1p
[lp-2 ] DEBUG 2024/08/28 13:59:10 charge total import: 0.319kWh
[lp-2 ] DEBUG 2024/08/28 13:59:10 charger status: A
[lp-2 ] ERROR 2024/08/28 13:59:10 charger disable: set charging profile: Rejected
[site ] DEBUG 2024/08/28 13:59:10 ----
[lp-1 ] DEBUG 2024/08/28 13:59:10 charge power: 1684W
[lp-1 ] DEBUG 2024/08/28 13:59:10 charge currents: [6.84 0 0]A
[lp-2 ] DEBUG 2024/08/28 13:59:10 charge power: 0W
[lp-2 ] DEBUG 2024/08/28 13:59:10 charge currents: [0 0 0]A
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:59:10 power: 1683.9W
[circuit-AutomaatLaadpaalVoortuin] DEBUG 2024/08/28 13:59:10 current: 6.84A
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:59:10 power: 0W
[circuit-AutomaatLaadpaalOprit] DEBUG 2024/08/28 13:59:10 current: 0A
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:59:11 power: -1523.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/08/28 13:59:11 current: 5.14A
[site ] DEBUG 2024/08/28 13:59:11 pv power: 5217W
[site ] DEBUG 2024/08/28 13:59:11 grid meter: -1505W
[site ] DEBUG 2024/08/28 13:59:12 grid powers: [212 -916 -836]W
What type of operating system are you running?
Docker container
Version
0.130.6
It depends on the car, as I need at least 2A per phase to load my Kona EV, so 6A (=+-4kwh).
It depends on the car, as I need at least 2A per phase to load my Kona EV, so 6A (=+-4kwh).
I am aware of that, apologies, but that is not the issue here. It is not 2A per phase but 6A per phase resulting at least minimum 6A aka 1.38kW or for 3 phases (since the signal is equal for all phases) 4.1kW
The charger also didn't charge with minPV or fast.
charger disable: set charging profile: Rejected
Looks like a duplicate, see open issues.
@andig 😄 a bit too fast, that is ALSO an issue and one that I am aware of, but that's my Wallbox Pulsar. the issue for which i logged one now is the Alfen, can you recheck please? 👍
@premultiply
Please try diagnosing yourself. Did this ever work, what did you change, does changing back help, does it worb without load balancing etc.. its up to you to find out what makes it „not work“. We simply dont have the capacity to do this 20 times a day…
Please try diagnosing yourself. Did this ever work, what did you change, does changing back help, does it worb without load balancing etc.. its up to you to find out what makes it „not work“. We simply dont have the capacity to do this 20 times a day…
Thanks, i completely understand and want to help.
It did work, it was never noticed because at peak solar consumption a lot of times there was already a bit of "drain of the overpressure" on that phase due to the fact that there was a load consuming some of the PV energy.
Only now the car was plugged in the middle of the day while PV was generating full power (18A) with almost no other consumers on that phase.
Therefore my conclusion is that load management is incorrectly "seeing" the amperage as ++ while it should be considered -- because it is available power.
DEBUG 2024/08/28 13:58:38 validate current: 14.3A + (0A -> 18.3A) > 20A capped at 5.67A
I interpret this log line as EVCC seeing that 14.3A is flowing through the circuit and thus it only has 5.67A available which is just a little bit short of 6A.
When a consumer (in this case the airco) started "sipping a bit of the amps" of the PV I see that EVCC concludes that the phase is not heavily used anymore and there are amps available. I interpret this based on the events at 13:58:30 up until the end at 13:59:11 .
Without load balancing there is no issue.
I interpret this log line as EVCC seeing that 14.3A is flowing through the circuit and thus it only has 5.67A available which is just a little bit short of 6A.
But, these 14.3A are negative, so going into the net. In my opinion, the available current value should be the difference between the highest grid current value and the limit.
So in that case
[site ] DEBUG 2024/08/28 13:58:37 grid currents: [1.45 -14.4 -3.83]A
it should be 20A - 1.45A = 18.55A
I interpret this log line as EVCC seeing that 14.3A is flowing through the circuit and thus it only has 5.67A available which is just a little bit short of 6A.
But, these 14.3A are negative, so going into the net. In my opinion, the available current value should be the difference between the highest grid current value and the limit.
So in that case
[site ] DEBUG 2024/08/28 13:58:37 grid currents: [1.45 -14.4 -3.83]Ait should be 20A - 1.45A = 18.55A
Indeed! That was my next post going to be. The problem is that the amps are not a negative value.
So your grid meter does not provide signed currents but they are signed according to the power sign? In that case, LM should take this "calculated" sign into account
@andig ich kann leider nicht prüfen, wie es sich verhält, wenn das Grid-Meter signed currents liefert. Ich vermute, LM nutzt die gemessenen Ströme direkt vom Grid-Meter?
Mein Shelly3EM gibt keine Vorzeichen aus. Somit ist der größte gemessene Wert = 6.74.
Aug 30 12:00:05 raspberrypi evcc[19927]: [circuit-main] DEBUG 2024/08/30 12:00:05 power: -3541.7W
Aug 30 12:00:05 raspberrypi evcc[19927]: [circuit-main] DEBUG 2024/08/30 12:00:05 current: 6.74A
Aug 30 12:00:05 raspberrypi evcc[19927]: [lpc ] DEBUG 2024/08/30 12:00:05 power: -3541.7W
Aug 30 12:00:05 raspberrypi evcc[19927]: [lpc ] DEBUG 2024/08/30 12:00:05 current: 6.74A
Aug 30 12:00:05 raspberrypi evcc[19927]: [site ] DEBUG 2024/08/30 12:00:05 grid meter: -3542W
Aug 30 12:00:05 raspberrypi evcc[19927]: [site ] DEBUG 2024/08/30 12:00:05 grid powers: [-481 -1565 -1496]W
Aug 30 12:00:05 raspberrypi evcc[19927]: [site ] DEBUG 2024/08/30 12:00:05 grid currents: [-2.35 -6.74 -6.42]A
Für LM würde ich bei circuit-main aber den größten tatsächlichen Wert, also -2.35, erwarten.
Oder denke ich da völlig falsch?
ich kann leider nicht prüfen, wie es sich verhält, wenn das Grid-Meter signed currents liefert.
ich habe meinen Shelly als Custom Meter nachgebaut und dort die currents entsprechend der phase-power mit Vorzeichen versehen. Das bestätigt meine Vermutung.
[circuit-main] DEBUG 2024/08/30 19:41:56 power: 54.37W
[circuit-main] DEBUG 2024/08/30 19:41:56 current: 2.82A
[site ] DEBUG 2024/08/30 19:41:56 grid meter: 54W
[site ] DEBUG 2024/08/30 19:41:56 grid currents: [-3.35 2.82 1.17]A
Hier wird der richtige Wert 2.82 genutzt.
So your grid meter does not provide signed currents but they are signed according to the power sign? In that case, LM should take this "calculated" sign into account
The grid meter delivers them (or at least EVCC somewhere "knows" either by the fact that the value comes in as a negative number or somebody wrote logic to take the negative kW sign and put it before the Amps) that it is a negative number, but in the LM functionality it apparently considers the number only, without the negative sign.
[site ] DEBUG 2024/08/28 13:58:37 grid currents: [1.45 -14.4 -3.83]A
@VolkerK62 my german is not so good, do we agree and are we seeing the same things or do I misinterpret you?
@hyperbart sorry, my english is not so good. So I wrote to andig in german, to make clear, what I have found out.
We aggree. As I wrote, the loadmanagement is working with the original sign from the meter ( in your case always positive) and not with the calculated sign, based on the phase powers sign.
I‘ll check if phase power correction is being applied here. I take
evcc meter
shows unsigned currents, too?
yes, unsigned
pi@raspberrypi:~ $ evcc meter grid
[main ] INFO 2024/08/31 15:10:42 evcc 0.130.6
[main ] INFO 2024/08/31 15:10:42 using config file: /etc/evcc.yaml
[db ] INFO 2024/08/31 15:10:42 using sqlite database: /var/lib/evcc/evcc.db
[mqtt ] INFO 2024/08/31 15:10:43 connecting evcc-2066606010 at tcp://localhost:1883
[mqtt ] DEBUG 2024/08/31 15:10:43 tcp://localhost:1883 connected
Power: -23W
Energy: 6004.1kWh
Current L1..L3: 3.76A 4.42A 8.35A
Voltage L1..L3: 240V 237V 237V
Power L1..L3: -870W -1019W 1865W
Do I understand correctly that:
evcc charger(i.e. device itself) delivers unsigned currents- loadpoint correctly handles signed currents
- circuit again sees unsigned currents
Which component do we have the issue with in this case: the charger? Grid meter?
Worth noting that- due to missing configuration- its unclear what grid meter even causes the issue. Closing.
The problem is the grid meter. It delivers unsigned currents and unfortunately the inverter only feeds into one phase. Due to these circumstances, the main circuit prevents the charging from starting.
But you are right.
@hyperbart The configuration and the output of evcc meter are missing
Hey guys, no problem. Please find it below:
meters:
- name: HuisMeter
type: template
template: eastron
id: 1
host: 192.168.4.184
port: 8899
usage: grid
modbus: tcpip
@VolkerK62 meter is a bit more difficult since I am running EVCC in a docker. Let me know if it is strictly necessary, I will boot up my test VM and run EVCC natively.
Let me know if it is strictly necessary
I guess, it is. Because this will (hopefully) show the unsigned currents, which is the main problem in this case.
Eastron template has phases powers, so this should already work. Re Docker: why not simply
docker run -v <mount config> evcc/evcc evcc meter
Eastron template has phases powers, so this should already work. Re Docker: why not simply
docker run -v <mount config> evcc/evcc evcc meter
Danke @andig , indeed, pretty easy.
[main ] INFO 2024/09/01 12:05:38 using config file: /etc/evcc.yaml
[db ] INFO 2024/09/01 12:05:38 using sqlite database: /root/.evcc/evcc.db
HuisMeter
---------
Power: 591W
Energy: 27624.5kWh
Current L1..L3: 1.09A 4.19A 4.16A
Power L1..L3: 79.8W -421W 971W
pvHuis
------
Power: 3724W
Energy: 41916.9kWh
Current L1..L3: 0A 15.7A 0A
Voltage L1..L3: 0V 238V 0V
Power L1..L3: 0W 0W 0W
pvTuinHuis
----------
Power: 675W
Energy: 11145.5kWh
Current L1..L3: 0A 0A 2.81A
Voltage L1..L3: 0V 0V 242V
Power L1..L3: 0W 0W 675W
Thank you. Spotted the bug. Reading sign-corrected currents from loadpoint works fine but reading directly from meter seems to be missing phase correction.
It would be great if you could test the PR before merging.
@andig your changes are pushed to the nightly this night, correct? Tomorrow I should be able to run the meter command again on your nightly and I should see the change, correct?
Let me know if I need to do anything else, I am here to help/execute.
It would be great if you could test the PR before merging.
[main ] INFO 2024/09/02 09:21:26 evcc 0.130.6 (f5547ba0)
[main ] INFO 2024/09/02 09:21:26 using config file: /etc/evcc.yaml
[db ] INFO 2024/09/02 09:21:26 using sqlite database: /root/.evcc/evcc.db
HuisMeter
---------
Power: -128W
Energy: 27655.7kWh
Current L1..L3: 1.03A 1.68A 0.385A
Power L1..L3: 85W -225W 13W
pvTuinHuis
----------
Power: 111W
Energy: 11152.7kWh
Current L1..L3: 0A 0A 0.541A
Voltage L1..L3: 0V 0V 219V
Power L1..L3: 0W 0W 111W
pvHuis
------
Power: 545W
Energy: 41938.9kWh
Current L1..L3: 0A 2.47A 0A
Voltage L1..L3: 0V 224V 0V
Power L1..L3: 0W 0W 0W
Do not look like expected yet.
Let's not confuse things please. I've fixed the circuit. evcc meter will still show exactly what's being measured.
Let's not confuse things please. I've fixed the circuit.
evcc meterwill still show exactly what's being measured.
For reference, Andi, I hope this confirms your fix, I am now seeing this in logging: (my interpretation of logging is that your fix works: negative power consumption 👍 and now the amps are also showing as negative 👍 and the maximum observed roll up value of all phases is now the highest mathematical number 👍 , not the absolute number as before 👍 )
@premultiply @andig
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:46 power: -2972.1W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:46 current: 1.12A
[site ] DEBUG 2024/09/02 13:42:46 pv power: 5146W
[site ] DEBUG 2024/09/02 13:42:46 grid meter: -2990W
[site ] DEBUG 2024/09/02 13:42:47 grid powers: [82 -2303 -767]W
[site ] DEBUG 2024/09/02 13:42:47 grid currents: [1.12 -9.86 -3.27]A
[site ] DEBUG 2024/09/02 13:42:47 site power: -2980W
[site ] DEBUG 2024/09/02 13:42:50 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:52 power: -2986.7W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:52 current: 1.12A
[site ] DEBUG 2024/09/02 13:42:52 pv power: 5145W
[site ] DEBUG 2024/09/02 13:42:52 grid meter: -2985W
[site ] DEBUG 2024/09/02 13:42:53 grid powers: [81 -2302 -770]W
[site ] DEBUG 2024/09/02 13:42:54 grid currents: [1.12 -9.89 -3.27]A
[site ] DEBUG 2024/09/02 13:42:54 site power: -2975W
[site ] DEBUG 2024/09/02 13:42:55 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:57 power: -2943.6W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:42:57 current: 1.12A
[site ] DEBUG 2024/09/02 13:42:57 pv power: 5148W
[site ] DEBUG 2024/09/02 13:42:57 grid meter: -2965W
[site ] DEBUG 2024/09/02 13:42:58 grid powers: [81 -2277 -769]W
[site ] DEBUG 2024/09/02 13:42:59 grid currents: [1.11 -9.76 -3.31]A
[site ] DEBUG 2024/09/02 13:42:59 site power: -2955W
[site ] DEBUG 2024/09/02 13:43:00 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:01 power: -2899W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:01 current: 1.12A
[site ] DEBUG 2024/09/02 13:43:01 pv power: 5142W
[site ] DEBUG 2024/09/02 13:43:01 grid meter: -2964W
[site ] DEBUG 2024/09/02 13:43:02 grid powers: [82 -2257 -773]W
[site ] DEBUG 2024/09/02 13:43:03 grid currents: [1.11 -9.79 -3.27]A
[site ] DEBUG 2024/09/02 13:43:03 site power: -2954W
[site ] DEBUG 2024/09/02 13:43:05 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:06 power: -2967.6W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:06 current: 1.12A
[site ] DEBUG 2024/09/02 13:43:06 pv power: 5147W
[site ] DEBUG 2024/09/02 13:43:06 grid meter: -2946W
[site ] DEBUG 2024/09/02 13:43:07 grid powers: [83 -2283 -761]W
[site ] DEBUG 2024/09/02 13:43:07 grid currents: [1.11 -9.82 -3.28]A
[site ] DEBUG 2024/09/02 13:43:08 site power: -2936W
[site ] DEBUG 2024/09/02 13:43:10 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:12 power: -2967.9W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:12 current: 1.12A
[site ] DEBUG 2024/09/02 13:43:12 pv power: 5152W
[site ] DEBUG 2024/09/02 13:43:12 grid meter: -2968W
[site ] DEBUG 2024/09/02 13:43:13 grid powers: [83 -2296 -774]W
[site ] DEBUG 2024/09/02 13:43:13 grid currents: [1.11 -9.85 -3.28]A
[site ] DEBUG 2024/09/02 13:43:13 site power: -2958W
[site ] DEBUG 2024/09/02 13:43:15 ----
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:17 power: -2983.8W
[circuit-AutomaatNetaansluiting] DEBUG 2024/09/02 13:43:17 current: 1.11A
[site ] DEBUG 2024/09/02 13:43:17 pv power: 5149W
[site ] DEBUG 2024/09/02 13:43:17 grid meter: -2976W
[site ] DEBUG 2024/09/02 13:43:18 grid powers: [81 -2293 -766]W
[site ] DEBUG 2024/09/02 13:43:19 grid currents: [1.11 -9.87 -3.27]A
[site ] DEBUG 2024/09/02 13:43:19 site power: -2966W
[site ] DEBUG 2024/09/02 13:43:20 ----
Sounds good- and much more so if it works for you :)