Improvement: Reset alarm and clear alarm history list
This works on bosch 3800i at least...could work on other systems also. What I noticed sometimes it's not possible to write 255, I wonder if it's somehow related if the alarm is really active or not. Because in those cases, I can not even reset it on the pump, it does not go away.
controller(0x09) -W-> boiler(0x08), ?(0x05), data: FF (offset 8)
But it seems to work, had alarm on the UI code 3071 and run this custom entity with value 255:
and the alarm went away
controller(0x09) -W-> boiler(0x08), ?(0x05), data: 01 (offset 42)
And this clears the alarm history list from the UI/pump:
with value 1
and if there is no active alarm... it also complains. Which I think is pretty obvious. :) 000+00:34:09.131 W 2455: [command] Command failed: invalid command 'alarm_reset' 000+00:34:09.131 E 2456: [emsesp] Write command failed invalid command (Not Found)
Thanks, the first command is same as boiler/reset maintenance, I'll add history option to the boiler/reset command.
@proddy Should we change the text from maintenance to message or add a message options with same ems-command as maintenance?
Thanks, the first command is same as
boiler/reset maintenance, I'll addhistoryoption to theboiler/resetcommand. @proddy Should we change the text frommaintenancetomessageor add amessageoptions with same ems-command asmaintenance?
yes, let's rename!
yes, let's rename!
Hmm, i see that maintenance reset also verifies the reset by reading the maintenance message, that is not nessesery for message reset, so maybe better two options?
yes, let's rename!
Hmm, i see that maintenance reset also verifies the reset by reading the maintenance message, that is not nessesery for message reset, so maybe better two options?
yes we have to then.