centreon-plugins
centreon-plugins copied to clipboard
[hardware::pdu::eaton::snmp::plugin] not working on ePDU G3 Switched
Hi,
We have EATON ePDU G3 Switched 04.02.0001 but the plugin [hardware::pdu::eaton::snmp::plugin] don't give correct information:
OK: PDU '**********' : temperature '1' status 'disconnected', temperature -273.1 C - humidity '1' status 'disconnected', humidity 0.00 % | '**********~1#sensor.temperature.celsius'=-273.1C;;;; '**********~1#sensor.humidity.percentage'=0.00%;;;0;100
checking pdu '**********'
temperature '1' status 'disconnected', temperature -273.1 C
humidity '1' status 'disconnected', humidity 0.00 %
The MIB: http://powerquality.eaton.fr/support/software-drivers/downloads/epdu-firmware.asp?cx=80
I can send a full snmpwalk by email.
Thanks for your help,
I need also the full snmpwalk of your equipment ?
I check the temperature as example. I use the table: temperatureTable (.1.3.6.1.4.1.534.6.6.7.7.1) with:
- temperatureProbeStatus (.1.3.6.1.4.1.534.6.6.7.7.1.1.3): 0 = disconnected, 1 = connected
temperatureName.1 = ""
temperatureProbeStatus.1 = INTEGER: 0
temperatureValue.1 = INTEGER: -2731
If you find other good OIDs, let's go!
You comment it if you have some other OIDs to monitor for your equipment.
Hello, I just find the oid for temp and humidity for this hardware eaton pdu g3
EATON_TEMP_OID=".1.3.6.1.4.1.534.6.8.1.2" EATON_HUMI_OID=".1.3.6.1.4.1.534.6.8.1.3"
Thanks a lot for your help