centreon-plugins
centreon-plugins copied to clipboard
[hardware::ups::powerware::snmp::plugin] environment and input-lines mode new OIDs
Hello,
I think the environment plugins needs an update.
Since 2.0.* firmware version on Eaton Network-M2 cards, the environment and Input-Lines plugins return "not a single value". Eaton support confirmed that the OIDs for the servicehave changed, and Centreon Support told me the only way to fix that is requesting update on GitHub.
Thanks a lot for your help !!
Hello @dantes549
Thanks. Could you obtain the new mibs from the Eaton support and share it with us. Also, a snmpwalk from your device could help. Feel free to send it to [email protected] and/or [email protected].
Thanks
Hello,
Do you have any news ?
Thanks,
Regards
The part xupsEnvironment is not populated anymore. It could be in .1.3.6.1.4.1.534.6.8.1 (eatonSensor). But the branch is empty: .1.3.6.1.4.1.534.6.8.1.1.1.0 (sensorCount) = INTEGER: 0
Need to ask of equipment support.