Error : TIMEOUT during backend server running

Open josephyou7 opened this issue 2 years ago • 1 comments

Current Behavior

I am trying to make backend server with node. It is running fine with attached program at first time but it has error after short 2 min. long 30 min.
< Error Message > C:\react-app\prodboard\backend\node_modules\ethernet-ip\src\controller\index.js:654 throw new Error(<SCAN_GROUP>\n ${e.message}); ^ Error: <SCAN_GROUP> TIMEOUT occurred while writing Reading Tag Group. at C:\react-app\prodboard\backend\node_modules\ethernet-ip\src\controller\index.js:654:31 at async Controller.scan (C:\react-app\prodboard\backend\node_modules\ethernet-ip\src\controller\index.js:647:13)

Your Environment

  • npm v9.8.1
  • NPM ethernet-ip 1.2.5
  • Node Version Node.js v18.17.1
  • Operating System window 10 Pro

plc_server.txt

josephyou7 avatar Sep 28 '23 19:09 josephyou7

try const PLC = new Controller(false); on line 15 to use unconnected messaging. Windows especially can cause a node process loop to pause for a few seconds which will disconnect you when using connected messaging.