Scada-LTS
Scada-LTS copied to clipboard
Virtual datapoint in attractor change type does not load attraction point variable.
Describe the bug When a numeric virtual datapoint of the attractor change type is being created, it does not load the variables that have just been created in the same datasource, it only loads the variables previously created before the creation of the datasource and current datapoint.
To Play Steps to reproduce the behavior:
- Create a virtual datasource then create a numerical datapoint without change;
- Next, create a numerical datapoint of the attractor type, in the "attraction point" it does not load the datapoint created in step 1;
Expected behavior It was expected that the datapoint created in step 1 would be loaded.
Screenshots
Desktop (please complete the following information):
- OS: Windows 10 64bit
- Browser: Chrome 112.0.5615.49
- Version: from ScadaBR 1.1/1.2
Additional context A way around the problem is: After step 1, update the page to create the datapoint with the point of attraction, in this case the variable created previously will be loaded.