The PR also adds config for a couple of electricity meters I've been testing with, Carlo Gavazzi EM111 and EM340.
@bastischubert any chance you can test if TCP support still works with this patch? I only have RS485 devices here with me. @RichiH said on IRC that you might be able to help :)
I'll test on monday when i'm back from vacation☺️
You can use https://github.com/3cky/mbusd as a serial to RTU converter, I have been using it for a while to use modbus_exporter with a cheap USB RS-485 adapter. Thank you for working on serial support!
This functionality is broken when using more than one subtarget on the same target. The problem is that serial communication is, well, serial, and prometheus might scrape two targets simultaneously, confusing the modbus code.
I haven't had any luck figuring out how to make sure only one thing happens at a time on the rs485 serial bus. Does anyone have input on how to achieve this? I was hoping MaxRequestsInFlight: 1
on the promhttp handler at the very the end of modbux_exporter.go would help, but it seems a new handler is made for each request by the router/mux, so that did nothing.
Any input would be appreciated. Otherwise I will sadly have to close the PR since I have no idea how to fix it.
@SuperQ can you help with making certain that sequentiality is ensured?
Does this appear per target only or would we hit the same with a lot of different targets at once? Global locks or sequencing is meh. If we end up in that situation, we would need to emit some metrics around this.
The issue is only per serial bus/device (for example /dev/ttyUSB0). The serial device is called target
in the modbus_exporter code. So only one subtarget (power meter) per target (serial device) at a time.
A lot of different targets at once is fine (as in, different serial devices /dev/ttyUSB0
and /dev/ttyUSB1
and /dev/ttyUSB2
can be hit at the same time).
When using relabelling the targets in prometheus.yml become sub_targets in modbus_exporter, so it is a bit confusing. But I think the above should be clear, see also the log snippet in the next comment :)
This log snippet shows the issue - all sub_target
(meters) are on /dev/ttyUSB0
(the serial bus) and prometheus is scraping sub_target
2 and 7 too close to eachother, so the underlying modbus code gets confused:
INFO[109961] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '5' source="modbus_exporter.go:130" INFO[109968] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '8' source="modbus_exporter.go:130" INFO[109970] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '1' source="modbus_exporter.go:130" INFO[109972] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '10' source="modbus_exporter.go:130" INFO[109989] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '4' source="modbus_exporter.go:130" INFO[109992] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '7' source="modbus_exporter.go:130" INFO[109992] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '2' source="modbus_exporter.go:130" ERRO[109994] failed to scrape metrics for module 'carlo_gavazzi_em_et_3xx_series,' target '/dev/ttyUSB0', sub_target '2': metric 'emet3xx_phase_voltage_volts', address '300000': serial: timeout source="modbus_exporter.go:148" ERRO[109994] failed to scrape metrics for module 'carlo_gavazzi_em_et_1xx_series,' target '/dev/ttyUSB0', sub_target '7': metric 'emet1xx_consumed_kvarh_total', address '300018': serial: timeout source="modbus_exporter.go:148" INFO[109995] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '9' source="modbus_exporter.go:130" INFO[110004] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '6' source="modbus_exporter.go:130" INFO[110020] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '5' source="modbus_exporter.go:130" INFO[110028] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '8' source="modbus_exporter.go:130" INFO[110030] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '1' source="modbus_exporter.go:130" INFO[110032] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '10' source="modbus_exporter.go:130" INFO[110049] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '4' source="modbus_exporter.go:130" INFO[110052] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '7' source="modbus_exporter.go:130" INFO[110052] got scrape request for module 'carlo_gavazzi_em_et_3xx_series' target '/dev/ttyUSB0' and sub_target '2' source="modbus_exporter.go:130" ERRO[110052] failed to scrape metrics for module 'carlo_gavazzi_em_et_1xx_series,' target '/dev/ttyUSB0', sub_target '7': metric 'emet1xx_firmware_revision', address '300771': resource temporarily unavailable source="modbus_exporter.go:148" ERRO[110054] failed to scrape metrics for module 'carlo_gavazzi_em_et_3xx_series,' target '/dev/ttyUSB0', sub_target '2': metric 'emet3xx_phase_voltage_volts', address '300000': serial: timeout source="modbus_exporter.go:148" INFO[110055] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '9' source="modbus_exporter.go:130" INFO[110064] got scrape request for module 'carlo_gavazzi_em_et_1xx_series' target '/dev/ttyUSB0' and sub_target '6' source="modbus_exporter.go:130"
OK, after a bit of fiddling this actually works really well now. I had to update the goburrow/modbus dependency because I hit an old bug they fixed since then. I solved the sequentiality requrement by wrapping the scrape in a mutex for serial scrapes. This means if one thread is already using the serial bus another thread will have to wait. I've added two new metrics to track the mutex stuff, a counter to total how many seconds are spent waiting for a mutex lock, and a gauge to show how many are waiting right now.
This leave one open issue, I don't have a system with two serial busses right now, but the mutex should be serial bus specific (there is no need to make a scrape on serial bus /dev/ttyUSB1 wait for /dev/ttyUSB0 to finish).
Before I dig into solving that (I do not have any systems with multiple serial adapters attached to seperate rs485 busses handy to test) I would like to request a review to make sure what I have now will be accepted when I finish the PR. Maybe @SuperQ can take another look? Thanks!
Hi, thanks for this feature! I tried to test it, and facing one issue with this config:
modules:
# https://www.owen.ru/uploads/re_mv110-224.2a_1822.pdf
- name: "owen_mv110"
protocol: 'serial'
baudrate: 9600
databits: 8
parity: "N"
stopbits: 1
timeout: 3000
metrics:
- name: "mv110_sensor"
help: "represents the current reading of analogue sensor"
labels:
input: "1"
address: 300004
dataType: float32
endianness: big
metricType: gauge
- name: "mv110_sensor"
help: "represents the current reading of analogue sensor"
labels:
input: "2"
address: 300010
dataType: float32
endianness: big
metricType: gauge
It successfully retrieves the metric only if SINGLE metric is defined in modbus.yml. If I add one more metric, i'm getting a bunch of various errors, such as, timeout, CRC error or that another device (id=4) responded instead of actual one with sub_module=32. It looks to me that two requests are sent to serial port at the same time and so collision happens? Maybe I'm wrong.
Like so:
failed to scrape target '/dev/ttyUSB0' sub_target '32' with module 'owen_mv110': failed to scrape metrics for module 'owen_mv110', target '/dev/ttyUSB0', sub_target '32': metric 'mv110_sensor', address '300010': modbus: response slave id '4' does not match request '32'
failed to scrape target '/dev/ttyUSB0' sub_target '32' with module 'owen_mv110': failed to scrape metrics for module 'owen_mv110', target '/dev/ttyUSB0', sub_target '32': metric 'mv110_sensor', address '300010': serial: timeout
failed to scrape target '/dev/ttyUSB0' sub_target '32' with module 'owen_mv110': failed to scrape metrics for module 'owen_mv110', target '/dev/ttyUSB0', sub_target '32': metric 'mv110_sensor', address '300010': resource temporarily unavailable
HW setup should be fine, since, I can poll multiple metrics using zabbix https://github.com/v-zhuravlev/libzbxmodbus and also I can get data using modpoll utility.
Sample request I'm using: http://192.168.15.200:9602/modbus?target=/dev/ttyUSB0&sub_target=32&module=owen_mv110
sounds like you might be scraping faster than your serial bus or devices can keep up, how often are you scraping and how long does a scrape take and how many targets do you have? remember, a serial bus is serial :)
I haven't forgotten about this patch and I will get back to it soon, I am currently pressed for time
Just scraping ONCE by manually hitting the URL of the modbus_exporter: http://192.168.15.200:9602/modbus?target=/dev/ttyUSB0&sub_target=32&module=owen_mv110 ... And problem only arises if more than one registry should be scraped. I understand that serial port should be used only by single entity, but it is only modbus_exporter trying to scrape something. I'll try dig more into this....
(Just to track this, I keep clicking the "Approve and Run" on the tests)
@tykling what's the status on your end? Does serial work in production?
@bastischubert do you currently have hardware to test TCP against?
Hmm, in this round of tests, even more fail than the last round. See above for details, @tykling
hey :)
Yes, serial works in production, even with multiple serial ports (without parallel scrapes messing anything up). I am very happy with it actually. I also tested TCP a while back and it works well.
But this PR is a mess. I fucked up a merge a while back so the branch has weird history with a bunch of commits that are not relevant. I have been meaning to close it and open a new "fresh" PR.
I also have a bunch of questions about the PR and the general direction you want to take with the project.
- a while back you said that you wanted
modbus.yml
to be like thesnmp.yml
file in thesnmp_exporter
- meaning you wanted it to be "ready to run" and slowly grow as new devices are added. For this reason I have included the devices I use withmodbus_exporter
inmodbus.yml
in this PR, but I don't see any other devices added. Did I misunderstand something? Do you want device registers inmodbus.yml
or not? - The devices I monitor have quirks which required new features in the code. The
offset
feature where a value is offset in a combined register. And a few days ago I had to add a new weird datatype which may or may not exist elsewhere, where a float64 is put into two int32 fields. The first int32 field has the integer part of the number and the next has the decimals. But the MSW of the decimals is always 0 so it requires some fiddling. This feels a bit weird to put into the exporter because I doubt many other devices use such weird registers. But otherwise it wont work. Thoughts? Do you want these two features in a different PR?
I think back ages ago when I first forked this there was not much in the way of tests so I haven't written any. But I will take a look at the failing tests and see what I can do. I am not very experienced with Go, this has been my very first real adventure with it in fact :)
Nice to hear it's working in prod!
Feel free to open a new PR, or clean up locally and force-push into this one. Both works.
Yes, we want to collect more default configs, but there's not a huge inrush of configs... Feel invited to add everything you have.
Modbus has a lot of weird warts -- As long as there's a sane way to express those quirks in declarative configuration, I'd err on the side of supporting the weird stuff.
Any help with the tests, or new tests, appreciated. This is more a work of love and passion by a bunch of people without the hardware to actually test the software, so every bit helps.