Open MarcelloDavis opened this issue 2 years ago • 3 comments

Hello,

I am asking myself if it is possible for the slave device to read out PDOs that are not directly adressed to it by the master device? Since the EtherCAT frame is transferred through all devices and sent back to the master, I thought that it may be possible to access the data on the fly? Or does one have to configure the slave device on the EtherCAT-master in order to be able to access any PDO?

Thanks in advance!

MarcelloDavis avatar Jun 07 '22 11:06 MarcelloDavis

The slave doesn't have access to the frame, it can only access the DPRAM. For logic LRW PDOs that access is programmed via the FMMU by the master and the FMMU is read-only from the PDI, so you can't set it up from the slave.

nakarlsson avatar Jun 09 '22 12:06 nakarlsson

@MarcelloDavis , can we close this issue?

nakarlsson avatar Jun 15 '22 18:06 nakarlsson

@MarcelloDavis , can we close this issue?

Yes, and thank you very much for your help!

MarcelloDavis avatar Jun 18 '22 09:06 MarcelloDavis