Hi, @mariorl Yes, it'd be great if would exist a data field in general view (side / top menu) showing current logged user. Normally, when the token expires, the sign...

@rvbatista, I am using TM221CE24R model. I have used, as you suggested, modscan. Scanning 100 coils (addressing from 1 to 100), I've noticed that coil 41 is changing its value...

What's strange is that I changed Q0.4 with Q0.5 and still coil 41 is changing it's value accordingly with Q0.5 value. Shouldn't have been another address instead of 41?

Hi, @rvbatista, unfortunately I didn't figure out. The TM221CE24R PLC has 8 DO (DigitalOutputs). On it can be added DO extensions. A DO extension has outputs with address from Q1.0...

@rvbatista thanks for the reply! So the only way to read coil's status is to transfer its value to a %M internal bit and read it on FUXA. Maybe DOs...

Hi, I have encountered the same problem when using multiple bits on bitmask. For the same object (motor, pump, etc.) cannot set a color for each selected bit from bitmask....

Hi, I get the same error for Modbus RTU. Did you find any solution to this? My error message: `2024-04-12T11:16:53.352Z [ERR] 'ModbusRTU' _readMemory error! Error: Data length error, expected 11...

Hi, Do you have any update on this topic? It's a very important bug.

Hi, Thanks for your reply! It's ok as you wrote. It'd be useful if could be implemented bitmask on select value control so the user can change its text depending...

Hi, My function requires 2 word tags as parameters. When I click on `$WordsToReal`, tag selection window is opening. In the below image, I can select only one tag. On...