Modbus RTU - 6 Digit Holding Register

Open ensmartcontrols opened this issue 3 years ago • 2 comments

Hi, I deployed mbusd application in Tinker board R2.0 ,Tested with Normal Modbus Devices , It is communicating with well,

Now we are going to integrate Danfoss VFD using mbusd application, We got Modbus addressing as below. Whether mbusd will support on this.

Model: Danfoss Fc102 (Six Digit Holding Register) 415010- Running Hours 415020- Kwh Counter etc., DanfossFC102 (1).xls Herewith I attached Danfoss VFD Modbus Addressing Details.

Thanks & Regards,

K. L. Narayanan India

ensmartcontrols avatar Oct 19 '22 03:10 ensmartcontrols

Hello,

Since "six-digit" is just a form of representation for Modbus entities, mbusd should work OK with it if your Modbus TCP software is doing its part of the translation from 6-digit to standard function/register form.

3cky avatar Oct 28 '22 10:10 3cky

Hi,

It is communicating, thanks for your reply, It is delayed due to site commissioning, We completed Integration successfully, Thanks