CT Clamps not reading anything

Open smartroad opened this issue 3 years ago • 1 comments

Hi! I brought the kit from Mouser which has the SCT016-A16 CT clamps. I have plugged into the board and had to add my own 9V transformer as the kit was for 120 and I am on 240v. The voltage reads mostly right (just needs calibration) but I am getting nothing from the current reading when I try to monitor a 450W oil filled heater.

-edit- This is the kit: https://www.mouser.co.uk/ProductDetail/392-CSCIRCUITSETUP02

Am I missing something? As I read it I just need to clamp around the power lead and plug into the 3.5mm jack, power-up and it should read the current being consumed?

ct01 ct02

smartroad avatar Jan 27 '22 17:01 smartroad

I'm sorry, I overlooked your question initially.

Are the clamps around the hot wire only? If they are around the hot and neutral the readings will not be correct.

CircuitSetup avatar Mar 25 '22 17:03 CircuitSetup